19/44
EN
Description
Reason
Solution
Valve
Cylinder
Regulator
Point of use
regulator
Gas
Supply
Panel
Increase of
outlet pressure
& relief valve
opens
Leakage in
pressure regu-
lator seat
Repair by
manufacturer
Slight increase
of outlet pres-
sure & relief
valve does not
open
Inlet pressure
drop
No failure, nor-
mal operating
state
Slight increase
of outlet pres-
sure
Diff erence
between fl ow
pressure (with
gas fl ow) and
Zero Pressure
(without gas
fl ow)
No failure, nor-
mal operating
state
Slight drop of
outlet pressure
Diff erence
between fl ow
pressure (with
gas fl ow) and
Zero Pressure
(without gas
fl ow)
No failure, nor-
mal operating
state
Heavy drop of
outlet pressure
Required
fl ow to high
for pressure
regulator
Choose new
pressure
regulator for re-
quired pressure
and fl ow
Heavy drop of
outlet pressure
Leakage in
process gas
tubing
Check process
gas tubing
Outlet Pres-
sure to high
Wrong set-
tings for pres-
sure regulator
Adjust pressure
regulator set-
tings, readjust
pressure
regulator, main-
tenance
Outlet pres-
sure increase
immediately
all the way to
the stop or
outlet pressure
increases and
gets slowly
higher than set
value and relief
valve opens
Pollution or
damage of
pressure
regulator seat
“Creap“
Repair by
manufacturer
Содержание PTLH0FT
Страница 12: ...12 44 EN 3 TECHNICAL SPECIFICATIONS 3 1 DIMENSION SHEET POINT OF USE REGULATOR...
Страница 32: ...32 44 DE 3 TECHNISCHE DATEN 3 1 MASSBLATT ENTNAHMEDRUCKREGLER...
Страница 43: ......