20/44
EN
Description
Reason
Solution
Valve
Cylinder
Regulator
Point of use
regulator
Gas
Supply
Panel
Noise during
operation
Required
fl ow too high
for pressure
regulator
Choose new
pressure
regulator for re-
quired pressure
and fl ow
No changes of
valve control
when turning
the handwheel
Defect
handwheel be-
cause of too
high torque,
defect of
spindle, defect
of thread
Repair by
manufacturer
Moisture on
pressure regu-
lator (NO dew,
rain or snow)
Pressure regu-
lator withdraw
energy from
environment
through gas
expansion
No failure, nor-
mal operating
state
Icing on pres-
sure regulator
(NO dew, rain
or snow)
Pressure regu-
lator withdraw
energy from
environment
through gas
expansion, lim-
ited delivery
performance
from pressure
gas tanks, e.g.
N2O, CO2
No failure, nor-
mal operating
state ATTEN-
TION: keep
functionality of
contact gauges
in mind, raise
quantity of
pressure gas
tanks
This table is not exhaustive. For questions and ambiguities please contact manufacturer.
10. DISMANTLING AND DISPOSAL
Once the system has reached its end-of-life, it must be dismantled and disposed of in an environmentally
compatible way.
10.1. SAFETY NOTES FOR DISMANTLING AND DISPOSAL
WARNING!
•
Risk of injury through incorrect dismantling!
RESIDUAL ENERGY STORAGE, SHARP EDGED COMPONENTS, TIPS AND CORNERS ON AND IN THE
SYSTEM OR ON THE REQUIRED TOOLS CAN CAUSE INJURY.
•
arrange enough space for working
•
be careful with sharp edges
•
pay attention for order and cleanness
•
loose components can cause accidents
•
dismantle the components properly. Bear in mind that some of the components are heavy. Use lifting
equipment if necessary
•
secure the components against falling or toppling over