Chapter 4 - Maintenance, Page 4-12________________________________________________________
UV System Scheduled Preventive Maintenance – Cont.
3.
Test the Extractor Inspection Door Safety Proximity Switch.
(Caution: For the following tests Polycarbonate 100% Attenuation Safety Glasses must be worn.)
a)
Turn on the exhaust fan at the Command Center. The “UVi System On” green Status Light in each
Ventilator Section should be on.
b)
Open the Extractor Access Door at the left end of the Ventilator. The Blue “UVi System Standby”
Status Light should come on. If this action does not occur, immediately shut down the exhaust
fan at the Command Center. Refer to the Troubleshooting section of this manual for corrective
action.
c)
If there is more than one Ventilator section, repeat the tests above, 3a and 3b, for each section.
4.
Test the UV Module Access Door Safety Switch
(Caution: For the following tests Polycarbonate Safety Glasses must be worn.)
a)
Turn on the exhaust fan at the Command Center. The “UVi System On” green Status Light in each
Ventilator Section should be on.
b)
Open one UV Module Access Doors (Refer to Figure 4-11-3). The Blue “UVi System Standby”
Status Light should come on. If this action does not occur, immediately shut down the exhaust
fan at the Command Center. Refer to the Trouble Shooting section beginning on page 5-8 for
corrective action.
c)
If there is more than one Ventilator section, repeat the tests above, 4a and 4b, for each section.
5.
Test the ESP Cell Plunger Safety Switch
a)
Turn on the exhaust fan at the Command Center. The green ESP CELL STATUS LIGHT in each
Ventilator Section should be on.
b)
Open the ESP Cell Access Doors to release the Plunger Safety Switch. The Blue “UVi System
Standby” Status Light should come on. If this action does not occur, immediately shut down the
exhaust fan at the Command Center. Refer to the Trouble Shooting section beginning on page 5-
8 for corrective action.
c)
If there is more than one Ventilator section, repeat the tests above, 4a and 4b, for each section.
6.
Lamp Replacement
The UV Lamps need to be replaced after 13,000 hours of use. After 13,000 hours the Lamps will still
work but the performance of the Lamps decreases dramatically. The Gaylord Command Center has a
built-in UV hours of operation clock. Refer to the Technical Manual for the Gaylord Command Center
for complete operational instructions. If the Lamps have been in use over 13,000 hours they should
be replaced. Refer to Page 6-7
of this manual for detailed instructions for replacing Lamps.