Chapter 4 - Maintenance, Page 4-2_________________________________________________________
Operator Preventive Maintenance – Cont.
ESP Cell Rotation
To achieve maximum smoke removal it is recommended that the ESP Cells be rotated out, using spare
cleaned Cells. The recommended number of spare ESP Cells is equal to the number of Cells of the longest
Ventilator section. The number of Cells in a Ventilator section is shown in Table T-4-3-1.
A soak tank (Refer
to Figure 4-3-1) is recommended for each spare Cell to facilitate cleaning. The frequency of rotation is
based primarily on the type of cooking equipment the unit is serving, the number of hours per day of
operation, hot water temperature and pressure, and the type of detergent used. The recommended
Cell rotation frequency is shown in the Table T-4-3-1. It is important to develop a system to track the
rotation times. Refer to Appendix “C” for a Cell Rotation Frequency Log Chart that can be photocopied
for use in developing a system for rotation.
Note;
Spare Cells are optional and must be ordered with
the Ventilator or may be ordered from the Gaylord Parts Department.
At The End Of The Cooking
Day Special Attention
Should Be Given To
Wiping Clean The Baffle At
The Air Inlet Slot
Figure 4-2-1
Isometric Cutaway
At The End of the
Cooking Day These
Areas Should Be
Wiped Down
ESP Cell Access Door
Shown in Open
Position
Door Hook
Ladder Rail
Inside The
Canopy