7
Pro
line
Pro
line
4. Use a grey 6PC6 modular jack interconnect cable (item C) to connect the output port of the first luminaire to the input
port of the second (11D).
5. Repeat these steps to connect up to 100 luminaires per splitter output port (11E). Up to 500 luminaires can be
connected to the primary channel.
6. Snap-on two grey ferrite cores (item D) on the grey interconnect cable (item C) close to the 6P6C plugs.
7. Use the grey 6PC6 modular jack interconnect cables (item C) to connect the outport of a splitter to the inport of the
next (11B).
8. Use the black secondary channel (item comes with controller) (10G) to connect another 500 luminaires, in the same
way the luminaires are connected to the primary channel.
6
Warning!
Ensure the power cord and the controller cables do not touch any of the reflectors.
6
Warning!
Distribute number of luminaires evenly over daisy chains.
6
Warning!
Ensure the repeater bus connections are integrated in a correctly set up installation for best results.
6
Warning!
Boosters should never be used to expand.
6
Warning!
The maximum cable length per splitter is 250m (100 interconnect cables).
1
2
100
C
D
E
101
102
200
201
202
300
401
402
500
F
301
302
400
501 - 1000
B
A
G
11