GTD-3000TxW
Instruction Manual
8. Troubleshooting
9. Interface Configuration
8.1. Fault List
[Table 10. Fault List]
FAULT MESSAGE
DESCRIPTION & CONDITION
발생원인
[FAULT-02]
"SENSOR HIGH"
Sensor output is above ADC max. value.
Defective sensor module or transmitter
board ADC
[FAULT-03]
"SENSOR LOW"
Sensor output is below ADC min. value.
Defective sensor module or transmitter
board ADC
[FAULT-04]
"EEPROM ERROR"
Defective Transmitter EEPROM Checksum
Defective Transmitter Board EEPROM
[FAULT-05]
"+24V LOW"
It occurs when 24 V main input power is inputed
with voltage below 10 V.
Input power below 10V or defective Transmitter
ADC
[FAULT-06]
"ADC FAIL"
Defective Transmitter ADC
Defective Transmitter ADC
[FAULT-07]
"H/W REVISION"
H/W Version Error
Defective MPU inside Transmitter
[FAULT-08]
"SENSOR HUNTING"
When there is repeated hunting error in gas
measurement
sensor output status may be poor or check
for input power noise.
8.2. Recovery List
[Table 11. Recovery List]
No
CAUSE
SOLUTION
1
Defective Sensor Module
Change Sensor
2
Defective Transmitter Board ADC
Change Transmitter Board
3
Defective Transmitter Board EEPROM
1) Perform Factory Initialization then correct parameter and re-calibrate
2) Change sensor unit when the same problem occurs again
4
Defective MPU inside Transmitter
Change Transmitter Main Board
5
Poor Sensor Output Status
Change Sensor
6
Check Input Power Noise
Check External Input Voltage Noise Status
9.1. MODBUS RS485
TYPE
ADDRESS
BITS
DESCRIPTION
Measured Gas
Concentration
30001
BIT15~0
Gas Measurement (Integer/Decimal point is not considered)
High Scale Setting
30002
BIT15~0
High Scale Setting (Integer/Decimal point is not considered)
Alarm 1 Setting
30003
BIT15~0
Alarm 1 Setting (Integer/Decimal point is not considered)
Alarm 2 Setting
30004
BIT15~0
Alarm 2 Setting (Integer/Decimal point is not considered)
Gas detector status
value
10000
BIT0
Alarm 1 Active Status
BIT1
Alarm 2 Active Status
BIT2
Fault Active Status
BIT3
Maintenance Mode Status
BIT4
Test Mode Status
BIT5
Calibration Mode Status
BIT6
Reserved
BIT7
Toggle Bit (Bit reversal in 2 sec interval)
External Test
3
BIT0~7
Gas Detector Test Mode Setting
External Reset
2
BIT0~7
Exit Gas Detector Test Mode
9.1.1. Interface setting
9.1.2. MODBUS RS485 Address map
■ Data Format: RTU
■ Baud rate: 9600 bps
■ Data bits: 8bits
■ Stop bit: 1bits
■ Parity: Even
■ For details, please go to www. modbus.org
[Table 12. RS485 MODBUS Address 구성]