6. Detector Operation Flow
GTD-3000TxW
Instruction Manual
[Table 9. Menu Configuration Table]
LEVEL1
LEVEL2
DEFAULT
NAME
PARAMETER
ALARM PROGRAM
MODE
ALARM2 TYPE SEL.
(ALARM2 TYPE SELECT)
[INCREASE/ DECREASE]
INCREASE
ALARM2 LEVEL ADJ
(ALARM2 LEVEL ADJUST)
[ 1~Full Scale]
40
ALARM2 DEAD BAND
[ 0.0~ Full Scale의 10% ] %FS
0.0
ALARM2 TIME SET
[0~60] SEC
1
ALARM2 RELAY CTL
(ALARM2 RELAY CONTROL)
[ON / OFF]
ON
SENSOR MODE
FACTORY Mode
MAINTENANCE MODE
FACTORY Mode
485 MODBUS MODE
FACTORY Mode
DEVICE MODE
FACTORY Mode
VERSION MODE
FACTORY Mode
TEST MODE
FACTORY Mode
SYSTEM MODE
FACTORY Mode
7.1. PROGRAM MODE
PASSWORD
[**]
- Contacting "FUNC" key with the Magnet-bar for 2 s or longer in Measuring Mode enters Password
-
mode.
- After setting Password using "↑" or "↓" key, contact "FUNC" key.
PROGRMAMMABLE
MODE
- If password is correct, it enters Program mode.
- By contacting "↑" or "↓" key, mode changes in defined order.
-
(PROGRAMMABLE->CALIABRATION->ALARM->SENSOR ->MAINTENANCE->485 MODBUS ->DEVICE->
-
VERSION->TEST->SYSTEM)
GAS TYPE
[ DEFINE ]
- Mode that sets gas name type and contacting "↑" or "↓"key changes gas type.
-
(DEFIN. / USERG.)
- DEFINE is selected when a built-in gas name is used. USERG. Is selected to define the gas name
-
directly by a user.
- When a desired gas type is displayed, contact "FUNC" key to set the gas name and enter Program Mode.
GAS SELECT
[ COMB. ]
- Mode that sets gas name name and contacting "↑" or "↓"key changes gas name.
- When gas type is set to DEFIN., built-in gas names can be selected for use. When it is set to USER,
-
the user shall set gas name using 6 character for use. Characters allowed for use are number, capital
-
Alphabet, space, and period. When position is moved by setting characters, a cursor in black box shape
-
appears as shown in the figure on left.
USER GAS
[■ ]
UNIT SELECT
[ %LEL ]
- Mode that sets gas measuring unit and contacting "↑" or "↓" key changes gas measuring unit.
-
( % / %LEL / PPM / PPB ).
- When a desired gas measuring unit is displayed, contact "FUNC" key to set the unit and enter Program
-
Mode.
DECIMAL POINT
[ 100 ]
- Mode that changes decimal place and contacting "↑" or "↓" key changes decimal place.
-
(0.100/1.00/10.0/100)
- When a desired decimal place is displayed, contact "FUNC" key to set the decimal place and enter the
-
next Program Mode.
HIGH SCALE
[ 100 ]
- Mode that sets high scale value that should be displayed for full range. Contacting "↑" or "↓" key
-
increases or decreases the scale value. ( 1 ~ 9999 )
- When a desired high scale is displayed, contact "FUNC" key to set the high scale value and enter the
-
next Program Mode.
PASSWORD
[00]
- It is password setting mode. This password is checked when entering Program Mode.
- Default is set to "00".
- Set using "↑" or "↓" key then contact "FUNC" key to set the password and enter the next Program
-
Mode.
7. System Mode