16 

BOILER ROOM APPLICATION RECOMMENDATIONS 

46 

Gassero

 is strictly advising to use water softening unit before commissioning process for long term usage. Otherwise, system could 

harm because of undesirable substances. 
It is strictly advising to use plate heat exchanger, if there is floor heating system on line.  
The devices that are commissioned outside of the required conditions, could be out of warranty.  

Water Condition Range 

Total 

Hardness  

°d 

pH 

(Aluminium) 

pH 

(Stainless) 

Iron 

(Not Diluted) 

Condunctivity 

Flushing 

6,5-8,5 

7,5-9,5 

<10ppm 

≤2000µS/cm

 

It is mandatory to comply with BSRIA 

7593 (See: Gassero Flushing Process) 

Nitrite protection should not be used in boilers with aluminum heat exchangers

 

W

AT

ER

 C

ON

DI

TI

ON

S

 

As GASSERO, we recommend flushing in the system to prolong the life of system and boilers. No acid-based products should be used during flushing.

 

The boiler must be serviced annually. All this maintenance should be made by authorized service, water values and the water softening unit (resin, salt etc.) 

values should be measured and maintained by service

 

Depending on the water conditions specified in the table, the problems that may occur in the boiler heat exchanger could make out of warranty. 

The water used in the installation must be city-water. 

Never use well-water

 

Assembly and installation should made according to Gassero sample schemes.   

Boiler (primary) pump must be selected to in accordence with the required pressure and flow rate. 

The boiler (primary) pump must be in the direction of the installation return line to the boiler. 

The system operating pressure should match with the working pressure of boiler. Sales Engineers could give consultancy. 

All heat exchanger manufacturers; recommends to use of plate exchanger instead of the hydraulic separator for seperate the primary circuit and the secondary 

circuit. 

Domestic waste system could be used for condensate water. In system with a total power of 200 KW and above, a neutralization tank must be used. 

Boiler output and input diameters must be strictly followed, other equipment should be selected according to the this diameters. In order to install other 

equipment, the diameter of the boiler out should not be reduced.

 

It is mandatory to use a suitable diameter filter and check valve to the boiler return line pipe at each boiler turn. 

Please contact our service department about detail of collector connection in installation of floor type boiler. 

Additional zone control modules and sensors must be requested if there are equipment such as three-way valves and boilers that must be checked on the 

heating collector. Please contact our Sales Engineer for more information. 

Must use air separator and dirt separator with hydraulic separator. 

In case the plate heat exchanger is used instead of the hydraulic separator as the system separator, expansion tank must be placed in the primary circuit. 

If an automatic filling valve is used in the system, a water meter must be used for following how much water is added to the system. 

In cascade systems, the sensor housing must be placed on the hydraulic separator or on the secondary flow line. If the system is separated by a plate heat 

exchanger, place the sensor housing on the secondary circuit flow line. 

HY

DRA

UL

IC

 

 

6A fuses must be used for the power supply of the boilers. The electrical system must be grounded. 

EL

ECT

RI

AN

D FL

UE

 

Chimney connections must be made in accordance with the chimney types and regulations. 

The flue gas analysis measuring probe (probe hole) must be opened by the flue company for each boiler. 

Boiler chimneys should be extended by a minimum 1 meter from the boiler flue outlet direction and then connected to the chimney collector without elbows 

or with elbows. 

If the chimney connections passes over the boiler, the connections should be checked properly and water tightening should be provided. Water in the chimney 

due to leaks may cause the system out of warranty. Adequate ventilation should be provided for the boiler room. 

The operating pressure of the boilers in the natural gas installation is 21 Mbar. Therefore, it is necessary to use a regulator in the gas line. There should be a 

minimum distance of 1-2 meters between the regulator and the boiler gas flange. There should be discharge line after regulator for discharge of the excess air. 

GA

S A

ND

 O

TH

ER

 

In order to control the gas pressures, the manometer must be fitted before and after the regulator. 

Gassero boilers are manufactured for heating and domestic water. Not suitable for commercial or industrial purposes. 

GASSERO shall not be held responsible 

for any problems arising out of the design purpose.

 

Содержание ALUBOX X-treme 350

Страница 1: ... 115 125 150 ALUBOX X treme ALUBOX X treme 350 ALUBOX X treme 430 ALUBOX X treme 535 ALUBOX X treme 640 ALUBOX X treme 700LX ALUBOX X treme 710 INSTALLATION AND USER MANUAL FLOOR STANDING CONDENSING BOILERS EN ...

Страница 2: ...etpoints 39 10 2 Nominal Load Emission Settings 40 10 3 Minimum Load Emission Settings 40 10 4 Gas Pressure Switch 41 11 Maintenance 41 11 1 Maintenance Process 41 12 Energy Saving Recommendations 43 13 Disposal 43 14 Product Fiche 44 15 Troubleshooting 45 16 Boiler Room Application Recommendations 46 IMPORTANT PLEASE READ INSTRUCTIONS BELOW CAREFULLY BEFORE THE INSTALLATION AND USAGE 1 THIS MANUA...

Страница 3: ...equent repairs and modifications Boiler may not be used by persons with inadequate physical mental and perceptual capacity and without experience and knowledge 1 3 SAFETY INSTRUCTIONS IF GAS SMELLS Do not open or close the power switches do not touch the plugs or sockets Do not smoke Do not use your phone Close the gas valve immediately Ventilate the space by opening the doors and windows Notify e...

Страница 4: ...ANDARTS AND REGULATIONS This boiler is manufactured in accordance with the following directives and standards EN 15502 1 A1 EN 15502 2 1 A1 Directives EU 2016 426 Gas Appliances Regulation GAR 2014 30 EU Electromagnetic Compatibility EMC 2014 35 EU Low Voltage Directive LVD 92 42 EEC Boiler Efficiency These installation and maintenance instructions are prepared for the Floor Standing condensing bo...

Страница 5: ...ter quality and other environmental conditions CONSUMER RIGHTS Consumers can apply for complaints and appeals to consumer courts and consumer arbitration committees In case of defective goods a Withdraw from the contract by stating that it is ready to return the product b If all costs incurred do not incur excessive costs to request free repair of the product c Requesting the replacement of the pr...

Страница 6: ...s or by ignition sources Never switch off the power supply of the boiler when the air temperature falls below 0 C against the risk of freezing Read the FROST PROTECTION section ALUBOX X treme condensing boilers must be installed in spaces that have the necessary ventilation openings according to current standards and applicable regulations Do not modify the ventilation openings ventilation ducts v...

Страница 7: ...672 4 111 9 650 4 127 6 702 0 710 711 3 880 134 6 685 6 129 6 669 2 145 9 711 3 2 4 WARNING LABEL WARNINGS Read the technical instructions and user manual carefully before the commissioning Commissioning must be made by an authorized Gassero service The boiler must be located in a location that is separate from the living quarters and only in accordance with the ventilation legislation 2 5 PACKAGI...

Страница 8: ...8mm D2 106mm 106mm 106mm 106mm 106mm 106mm E DN100 PN6 DN100 PN6 DN100 PN6 DN100 PN6 DN125 PN6 DN100 PN6 E1 1340mm 1340mm 1340mm 1340mm 1360mm 1340mm E2 235mm 300mm 300mm 300mm 263mm 300mm F DN100 PN6 DN100 PN6 DN100 PN6 DN100 PN6 DN125 PN6 DN100 PN6 F1 664mm 664mm 664mm 664mm 647mm 664mm F2 88mm 115mm 115mm 115mm 65mm 115mm G Ø250mm Ø250mm Ø250mm Ø250mm Ø250mm Ø250mm G1 511mm 511mm 511mm 511mm 51...

Страница 9: ...Limit Thermostat 9 Pressure Sensor 10 Flow NTC Sensor 11 Return NTC Sensor 12 Automatic Air Vent 13 Flue Gas Sensor 14 Flue Gas Outlet 15 Syphon 16 Water Outlet Connection 17 Water Inlet Connection 18 Gas Inlet 19 Air Intake 20 Venturi 21 Syphon Sensor 22 Pressure Safety Valve 23 Drain Hose 24 Air Pressure Switch ALUBOX X treme 350 8 ...

Страница 10: ...ansformer 8 Limit Thermostat 9 Pressure Sensor 10 Flow NTC Sensor 11 Return NTC Sensor 12 Automatic Air Vent 13 Flue Gas Sensor 14 Flue Gas Outlet 15 Syphon 16 Water Outlet Connection 17 Water Inlet Connection 18 Gas Inlet 19 Air Intake 20 Venturi 21 Syphon Sensor 22 Pressure Safety Valve 23 Drain Hose 24 Air Pressure Switch 9 ...

Страница 11: ...ansformer 8 Limit Thermostat 9 Pressure Sensor 10 Flow NTC Sensor 11 Return NTC Sensor 12 Automatic Air Vent 13 Flue Gas Sensor 14 Flue Gas Outlet 15 Syphon 16 Water Outlet Connection 17 Water Inlet Connection 18 Gas Inlet 19 Air Intake 20 Venturi 21 Syphon Sensor 22 Pressure Safety Valve 23 Drain Hose 24 Air Pressure Switch 10 ...

Страница 12: ...ansformer 8 Limit Thermostat 9 Pressure Sensor 10 Flow NTC Sensor 11 Return NTC Sensor 12 Automatic Air Vent 13 Flue Gas Sensor 14 Flue Gas Outlet 15 Syphon 16 Water Outlet Connection 17 Water Inlet Connection 18 Gas Inlet 19 Air Intake 20 Venturi 21 Syphon Sensor 22 Pressure Safety Valve 23 Drain Hose 24 Air Pressure Switch 11 ...

Страница 13: ...ransformer 8 Limit Thermostat 9 Pressure Sensor 10 Flow NTC Sensor 11 Return NTC Sensor 12 Automatic Air Vent 13 Flue Gas Sensor 14 Flue Gas Outlet 15 Syphon 16 Water Outlet Connection 17 Water Inlet Connection 18 Gas Inlet 19 Air Intake 20 Venturi 21 Syphon Sensor 22 Pressure Safety Valve 23 Drain Hose 24 Air Pressure Switch 12 ...

Страница 14: ...ansformer 8 Limit Thermostat 9 Pressure Sensor 10 Flow NTC Sensor 11 Return NTC Sensor 12 Automatic Air Vent 13 Flue Gas Sensor 14 Flue Gas Outlet 15 Syphon 16 Water Outlet Connection 17 Water Inlet Connection 18 Gas Inlet 19 Air Intake 20 Venturi 21 Syphon Sensor 22 Pressure Safety Valve 23 Drain Hose 24 Air Pressure Switch 13 ...

Страница 15: ... 86 28 55 6 65 30 43 Water Flow 50 30 C m h 3 052 15 2 3 941 19 286 5 281 23 454 3 935 28 389 5 54 30 31 6 6 30 5 Hydraulic Loss kPa Gas flow 80 60 C m h 6 93 35 23 8 84 44 6 10 75 53 47 8 45 64 52 12 09 69 82 13 99 71 78 Gas flow 50 30 C m h 6 89 34 6 8 76 44 35 11 63 53 91 8 69 64 13 12 34 70 05 14 02 71 43 Maximum Gas Supply Pressure G20 mBar Minimum Gas Supply Pressure G20 mBar Flue Pressure P...

Страница 16: ...ork lift or pallet truck as shown In such transports the boiler must be properly fixed and secured The boiler must not be shaken or laid on its side during transport The boiler can also be moved on its own wheels after being lowered The wheels must always be secured and fixed when the transport is finished During the transportation safety rules must be followed and care must be taken against injur...

Страница 17: ... the table boiler will be considered out of warranty Total Hardness d pH Iron Not Diluted Conductivity STAINLESS EXCHANGER 1 00 7 5 9 5 10ppm 2000µS cm ALUMINUMEXCHANGER 1 00 6 5 8 5 10ppm 2000µS cm Gassero Water Specification DYNAMIC AND CHEMICAL WASHING FLUSHING In the newly established systems to aviod the possible substances in the installation metal shavings some oils residues of construction...

Страница 18: ...rer cannot be held liable for damages caused by water flow into the boiler or on the ground when excessive pressure is generated in the heating installation Safety valve must not be used as a means of draining water from the system Draining water of the safety valve can be very hot Beware of scalding 4 2 3 CONDENSATION WATER DRAIN Condensation water which is generated during to the combustion tran...

Страница 19: ...oiler and the water goes through the installation Only heat transfer occurs here Preferred for many purposes If the water in the system is very dirty chalky or corrosive If the working pressure of the system exceeds the working pressure of the boiler If a part or all of the system is required to operate with lower temperature values eg underfloor heating systems The plate heat exchanger must be us...

Страница 20: ...ter must be checked regularly When the air inlet filter becomes dirty Emission values would be deteriorated and efficient combustion wouldn t be achieved The accumulation of soot occurs in the heat exchanger Loud ignition and combustion occurs Overheating leakage and deformation would be observed in the flue system Manufacturer cannot be held liable for damages caused by dirty combustion air Don t...

Страница 21: ...V PUMP CONNECTION EXAMPLE The use of an unsuitable primary pump can result an uneconomic uncomfortable operation and damage to your boiler and your installation The manufacturer is not liable for damages that may arise from such situations 4 3 FLUE CONNECTIONS Flue and chimney connections must be carried out in accordance with applicable regulations and relevant standards Materials which are used ...

Страница 22: ...E certified flue pipes C83 It is a flue system which takes the combustion air from the outside with horizontal flue pipes and throws flue gas to the self contained negative pressure chimney For the operation of the boiler a grounded electrical supply 230 VAC 50Hz is required tolerance must be between 15 ve 10 Electric supply of the boiler must be cut off via a fuse during the maintenance Electrica...

Страница 23: ...LUE NEUTRAL YELLOW GROUND has to be connected to a 6A fuse 3 X 1 5 Q1 BOILER PUMP CABLE SECTION PICTURE CONNETION EXPLANATION RED RED BLACK BLACK BLACK WHITE YELLOW YELLOW BLACK BROWN BROWN BLACK BLUE BLUE BLACK BROWN BLUE PURPLE GREY YELLOW GREEN 2x1 5 PUMP PWM CONTROL 0 10 V It connects to frequency controlled modulating primary pumps 0 10 terminal It controls the modulation of the pump 2x1 5 Fl...

Страница 24: ...23 ...

Страница 25: ...24 ...

Страница 26: ...25 ...

Страница 27: ...OCI 351 Modbus Module 26 ...

Страница 28: ...s and vents Open the sensor housing cover by turning it counterclockwise to access the sensor connection terminal and the wall fixing holes Mark the fixing points on the wall and drill the wall using the storage box as a template Secure the box to the wall using the two anchors provided Connect the two wire cable from the boiler to the terminal box nonpolar Tighten the nut in the housing box to en...

Страница 29: ...tank should be used for condensate water occurring in systems with a total power o f 200 kW and above Pump Expansion Tank Safety Valve Air Seperator Deposit and Dirt Seperator Outdoor Sensor Water Softener UNit Temperature Sensor Globe Valve Termometer Manometer Non Return Valve Hydraulic Seperator Gas Regulator Strainer Neutralization Tank WATER SOFTENER UNIT HYDRAULIC SEPERATOR RADIATOR CIRCUIT ...

Страница 30: ... must be used in the system A neutralization tank should be used for condensate water occurring in systems with a total power o f 200 kW and above Pump Expansion Tank Safety Valve Air Seperator Deposit and Dirt Seperator Outdoor Sensor Water Softener UNit Temperature Sensor Globe Valve Termometer Manometer Non Return Valve Hydraulic Seperator Gas Regulator Strainer Neutralization Tank Air Relief V...

Страница 31: ...e Plate Heat Exchanger RADIATOR CIRCUIT DHW CIRCUIT FLOOR HEATİNG CIRCUIT MECHANICAL SCHEME WITH PLATE HEAT EXCHANGER Installation of 2 FLOOR STANDING CONDENSING BOILERS in cascade with 1 FLOOR HEATING CIRCUIT 1 RAD IATOR CIRCUIT 1 DHW CIRCUIT WATER SOFTENER UNIT Water Softener Unit must be used in the system A neutralization tank should be used for condensate water occurring in systems with a tot...

Страница 32: ...enance etc must be performed by authorized personnel Improper interventions may cause loss of life and property increased fuel consumption and deterioration in safe and comfortable operation Manufacturer cannot be held liable for any problems caused by incorrect adjustments and interventions Display symbols Comfort setting for heating Reduced heating setting for heating Frost protection setting fo...

Страница 33: ...dby mode pumps will be energised periodically mixing valves ran into middle position This function will be turned off automatically after the cycle FLUE FUNCTION E Used for flue gas emission measuring During this function boiler will be operated according to maximum adjusted temperature until it reach the exact value Then this function will be turned off automatically INFO BUTTON F Used for the di...

Страница 34: ...ress OK Turn the Navigation Knob to select Heating circuit 2 and press OK Adjust the desired room temperature and press OK Press ESC button to return upper menu and adjust other heating circuits REDUCED TEMPERATURE A temperature limit for the room temperature When the room temperature falls below the set temperature the boiler will be activated and keep the room temperature constant Factory settin...

Страница 35: ... unit etc in the system all personalized settings parameters fault resets will be made via the control panel E g Date and time adjustment Push OK button Select Time of day and date then push OK button again Push OK button for adjusment Push OK button to adjust hour and minute settings Turn the adjusment knob one click and set mounth and day with pushing OK button Push OK button to adjust the year ...

Страница 36: ...ess button 1x again Safety mode on with Heating off Temperature by frost protection Safety functions activated Controller Stop Mode Press button 3 sec 304 Controller Stopp mode insert setpoint Press button 3 sec again after 3 sec Main menu appears Press button 1x INFO Segment displayed Press button 1x again Status Boiler room temperature Press button 1x again room temperature minimum Status DHW ro...

Страница 37: ...ion 5960 parameter should set Consumer Request CC1 10V from configuration menu 2 5963 64 65 66 parameter should set for heat and value assignment 3 Heating Circuit 5710 and 5715 parameter should set OFF from configuration menu 4 DHW Domestic Hot Water Circuit sensor should be cancelled from boiler ...

Страница 38: ...l Frost protection 651 Preselection Period 1 652 Period Start Day Month tt MM 01 01 31 12 653 Periode End Day Month tt MM 01 01 31 12 658 Operating level Frost protection 661 Preselection Period 1 662 Period Start Day Month tt MM 01 01 31 12 663 Periode End Day Month tt MM 01 01 31 12 668 Operating level Frost protection 710 Comfort setpoint C Value from Line no 712 35 20 712 Reduced setpoint C 4 ...

Страница 39: ...ximum duration of the refill per charging 353 Common flow sensor B10 not available 85 BSB RF communication error 196 Maximum duration of the refill per week exceeded 371 Flow temperature 3 heating circuit 3 supervision 91 EEPROMerror lockout information 209 Fault heating circuit 372 Limit thermostat heating circuit 3 98 Extension module 1 error collective error 214 Monitoring of motor 373 Extensio...

Страница 40: ...X X TREME LX 700 G20 ALUBOX X TREME 350 ALUBOX X TREME 430 ALUBOX X TREME 535 ALUBOX X TREME 640 10 COMBUSTION ADJUSTMENTS These combution settings mentioned below must be issued by authorized GASSERO services Flue gas analyzer must be used during to the combustion adjustments ALUBOX X treme boilers are offer to sale after all required combusiton efficiency and safety controls Emission settings mu...

Страница 41: ...stem are open the condensate drain line is open the flue connections are gas tight and the pumps are running Due to the danger of burning and scalding be careful of the boiler and plumbing pipes which will become very hot 10 2 NOMINAL LOAD EMISSION SETTINGS 10 3 MINIMUM LOAD EMISSION SETTINGS Minimum load emission setting is done by measuring the CO2 value in the flue gas The following steps shoul...

Страница 42: ...l be ensured The loss of comfort will be prevented by avoiding possible faults errors When the emissions of waste gases released into the environment are controlled the environment will be protected Life time of the boiler installation and environment must be take into account information error fault histories should be evaluated Issues such as fault history operating times can be displayed via th...

Страница 43: ...ng the boiler with water check that the water treatment units are running and active A sample should be taken from the water filled in the boiler and the results of the analysis will be written to the service document Water gas air chimney and electrical connections will be checked Gas leakage control will be made For gas leakage control a gas detector or leakage detection sprays may be used Chimn...

Страница 44: ...h the applicable regulations Similarly local regulations will be followed for the packaging wastes Leaving the non functional units spare parts and packaging materials in the environment and leaving them accessible to children can be dangerous Such wastes must be treated in accordance with the applicable regulations Ignoring this warning may harm people animals and may cause property damage Manufa...

Страница 45: ... CE directives EU type inspection Module B has been made by Szutest in Brno laboratory Production process inspection has been made by Kiwa certification organisation in order to module D production process based on quality assurance Conformity marking CE 0063 This document has been prepared in order to EU 811 2013 regulation Electricity Consumption Temperature controls Product fiche ERP Informatio...

Страница 46: ...15 TROUBLESHOOTING 45 ...

Страница 47: ...y to use a suitable diameter filter and check valve to the boiler return line pipe at each boiler turn Please contact our service department about detail of collector connection in installation of floor type boiler Additional zone control modules and sensors must be requested if there are equipment such as three way valves and boilers that must be checked on the heating collector Please contact ou...

Страница 48: ...ed MANUFACTURER Gassero Isi Teknolojileri Sanayi Limited Sirketi İstanbul Endüstri ve Ticaret Serbest Bolgesi 4 Sokak No 8 34957 Tuzla Istanbul TURKEY Phone 90 216 394 09 85 86 87 Fax 90 216 394 24 91 www gassero com 200600120 15102019 1 ...

Отзывы: