Connect the Flue Gas Analyzer probe to the sampling point
on the flue adapter
.
Make sure that the Flue Gas Analyzer which will be
used to adjust the combustion settings is calibrated
and functioning correctly.
To run the boiler at nominal load;
Press and hold Heating Mode button for 3 sec.
«Controller Stop Function On» will be mentioned on the
screen
Modulation rate will be displayed in % by pressing the
Info button.
Press OK button and change the modulation rate to
%100 by turning the Adjusment Knob.
Press OK button to apply.
Turn the Nominal Gas Flow Adjustment Screw (A) clockwise
to increase the CO2 value. If you turn it counterclockwise, the
gas flow rate will decrease and therefore the CO2 value will
decrease.
Before operating the boiler at nominal load, ensure
that the valves in the system are open, the
condensate drain line is open, the flue connections
are gas-tight and the pumps are running.
Due to the danger of burning and scalding, be
careful of the boiler and plumbing pipes which will
become very hot.
10.2
NOMINAL LOAD EMISSION SETTINGS
10.3
MINIMUM LOAD EMISSION SETTINGS
Minimum load emission setting is done by measuring the
CO2 value in the flue gas. The following steps should be
followed for this instant measurement on a boiler operating at
minimum capacity.
To run the boiler at minimum load;
Press and hold Heating Mode button for 3 sec.
«Controller Stop Function On» will be mentioned on the
screen
Modulation rate will be displayed in % by pressing the
Info button.
Press OK button and change the modulation rate to %0
by turning the Adjusment Knob.
Press OK button to apply.
Turn the Minimum Gas Flow Adjustment Screw (D) clockwise
to increase the CO2 value. If you turn it counterclockwise, the
gas flow rate will decrease and therefore the CO2 value will
decrease.
40