Gas Detection (Australia) Pty Ltd Page 39 of 44
M-GDA-3000 Rev 1
11.11. How to configure in Device Mode
※
The operations in this chapter must not be allowed by general users.
After password has been confirmed, the detector goes into level1
mode.
Select DEVICE mode by touching “↑” or “↓” switch.
At the moment, if function key is touched, the detector will go into
submenu of DEVICE MODE.
This mode is to check the connection status of HART board.
If the board is connected, “CHECK” will be shown. Otherwise “EMPTY”
will be shown.
This mode is to set polling address of HART device.
The available value is between 0 and 63. (Default value is 0)
If polling address is not 0, the setting of current output mode is fixed to
be 4mA.
This mode is to check fixed current mode of HART device.
This value cannot be modified.
This mode is to check Device Code of HART device.
This value cannot be modified.
This mode is to check Serial Number of HART device.
This value cannot be modified.
This mode is to check Tag of HART device.
This value cannot be modified.
This mode is to check long tag of HART device.
Long strin
g can be shifted by touching “↑” or “↓” switch.
This string cannot be modified.
This mode is to check descriptor of HART device.
This value cannot be modified.
This mode is to check messages generated by HART device.
The messages cannot be modified.
This mode is to set Final Assembly number of HART device.
Available number is 0-100. (Default value is 0)