WARNING
Make sure that you choose a CT that is suitable for your
installation. CT’s of two output types can be used. 0-
333 mV or 0 – 5 A output range. For easy installation,
GARO recommends the 0-333 mV type when possible.
0–333 mV is only valid for GARO Entity Balance BASIC
and 0–5 Ais only valid for GARO Entity Balance
ADVANCED. (Take notice: 0-5 A output types of CT
clamps must never be exposed to open circuit
conditions.)
NOTE
This chapter shows the installation of the GARO Entity
Balance BASIC and the GARO 0-333 mV CT clamps
that are available as accessory. The process for the
GARO Entity Balance ADVANCED is similar.
8. Dismantle the CT wires and connect the CT clamps
to the load interface.
Use a wire ferrule (A) for strained wires (B).
NOTE
The PE coductor is internally connected to one of each
CT pole (no.1, 3, 5). This in order to provide a defined
voltage potential.
The input terminals 1, 3 and 5 are internally
connected to PE in the load Interface.
CT1-3: 0-333 mV (Basic)
CT1-3: 0-5 A (Advanced)
CT3
CT2
CT1
+
-
+
-
+
-
8 mm
CT2-/GND(Black) L
CT1-/GND (Black) L
CT2+ (White) K
CT1+ (White) K
CT3-/GND(Black) L
CT3+ (White) K
A
B