Prior to connecting the regulator, check the incoming line 

pressure, as these regulators can withstand a maximum 

pressure of ½ psi (14” WC). If the Line pressure is beyond 

this limit, a step-down regulator will be required. Double-

check the arrow forged onto the bottom of the regulator 

body which shows gas flow directions; it should point 

downstream to the appliance. The red air-vent cap is 

part of the regulator and should not be removed unless 

local codes require external venting.
Regulators  can  be  adjusted  in  the  field,  but  it  is 

recommended that they not be tampered with unless 

that part is known to be out of adjustment or serious 

pressure fluctuations are found to exist and can be solved 

no other way. Any adjustments to regulators must be 

made by qualified service personnel with the proper test 

equipment.
If a vent line from the gas appliance pressure regulator is 

used, it should be installed to the outdoors in accordance 

with local codes or, in the absence of local codes, with 

the National Fuel code, ANSI Z223.1, Natural Gas 

Installation Code, CAN/CGA-B149.1 or the Propane 

Installation Code, CAN/CGA-B149.2, as applicable.

Rigid Connections

Double-check any installer-supplied intake pipes visually 

and clear any dirt particles, threading chips, or other 

foreign matter before installing in a service line. Those 

particles will clog orifices when gas pressure is applied.

Flexible Couplings & Connectors

If  the  unit  is  to  be  installed  with  flexible  couplings 

and/or  quick-disconnect  fittings,  for  an  appliance 

equipped with casters, the installation shall be made 

with a heavy duty, AGA design-certified commercial 

flexible connector or at least ¾” NPT (with suitable strain 

relief’s) in compliance with the Standard for Connectors 

for Movable Appliances, ANSI Z21.69 or Connectors for 

Moveable Gas Appliances,CAN/CGA-6.16, and a quick-

disconnect device that complies with the Standard for 

Quick-Disconnect Devices for Use With Gas Fuel, ANSI 

Z21.41, or Quick-Disconnect Devices for Use with Gas 

Fuel, CAN1-6.9, and adequate means must be provided to 

limit the movement of the appliance without depending 

on the connector and the quick-disconnect device or 

its associated piping to limit the appliance movement 

and the location(s) where the restraining means may be 

attached to the appliance shall be specified.
Further, if the unit is to be installed on a non-combustible 

surface that is equipped with casters, means must be 

provided to limit the movement of the unit on this 

surface. An addendum included with these instructions 

indicates the location(s) where the restraining means 

may be attached to meet the above standards.

Manual Pilot Valve

Check all gas connections for leaks using a soapy solution 

before! Lighting any pilots. DO NOT USE AN OPEN 

FLAME TO CHECK FOR LEAKS! Putting an open 

flame beside a new connection is not only dangerous, 

but will often miss small leaks that a soapy solution 

would find.
All Garland appliances are adjusted and tested before 

leaving the factory, effectively matching them to sea 

level conditions. Adjustments and calibrations to assure 

proper operation may be necessary on installation to meet 

local conditions, low gas pressure, differences in altitude, 

variations  in  gas  characteristics,  to  correct  possible 

problems caused by rough handling or vibration during 

shipment, and are to be performed only by qualified 

service personnel.
These adjustments are the responsibility of the customer, 

installer and/or dealer and are not covered by the Garland 

warranty.
All burners are equipped with constant-burning pilots. 

These should be manually lighted immediately after the 

gas is turned on and the system is checked for leaks. An 

adjustment screw for each pilot is located on the gas 

manifold, and can be accessed through openings in the 

valve panel between the valve knobs.

INSTALLATION Continued

Содержание GXC24

Страница 1: ...d by a Garland authorized service agent using genuine Garland replacement parts Garland will have no obligation with respect to any product that has been improperly installed adjusted operated or not maintained in accordance with national and local codes or installation instructions provided with the product or any product that has its serial number defaced obliterated or removed or which has been...

Страница 2: ...Part 9229077 07 05 Page ...

Страница 3: ...oning And Setup 7 Air Supply And Ventilation 7 Gas Connection 7 Manual Shut off Valve 7 Pressure Regulator 7 Rigid Connections 8 Flexible Couplings Connectors 8 Manual Pilot Valve 8 Initial Pilot Light 9 Shut Down 9 Final Preparation 9 Cleaning And Maintenance 9 Daily GXC Series 9 Daily GXR Series 10 Periodic 10 Cleaning Stainless Steel 10 Service And Parts 10 ...

Страница 4: ...ssionally trained personnel Description GXC SERIES GXR SERIES 24 30 36 48 60 24 30 36 48 60 Width In mm 24 610 30 762 36 914 48 1219 60 1524 24 610 30 762 36 914 48 1219 60 1524 Depth In mm 31 3 8 797 All Models Height In mm 20 508 All Models No Burners 2 2 3 4 4 4 5 6 8 10 BTU Hr Nat Pro 90 000 90 000 135 000 180 000 180 000 72 000 90 000 108 000 144 000 180 000 Gas Manifold 3 4 NPT 3 4 NPT 3 4 N...

Страница 5: ...Coals SHIPPING INFORMATION Model No Description Total BTU Lbs Kg Cube Dimensions LxDxH In mm GXC24 24 Wide Broiler 90 000 283 128 30 762 x 40 1016 x 27 656 GXC30 30 Wide Broiler 90 000 338 153 36 914 x 40 1016 x 27 656 GXC36 36 Wide Broiler 135 000 391 177 42 1067 x 40 1016 x 27 656 GXC48 48 Wide Broiler 180 000 505 229 54 1372 x 40 1016 x 27 656 GXC60 60 Wide Broiler 180 000 620 281 60 1524 x 40 ...

Страница 6: ...as In the event you have any questions concerning the installation use care or service of the product write or call our Product Service Department WARNING All Garland Char Broilers must be connected only to the type of gas identified on the rating plate INSTALLATION General Installation IMPORTANT Safe and satisfactory operation of your equipment depends to a great extent on its proper installation...

Страница 7: ...oilers must be under a vent hood Filters and drip troughs should be part of any industrial hood but consult local codes before constructing and installing a hood Air movement should be checked during installation Strong exhaust fans in this hood or in the overall air conditioning system can product a slight vacuum in the room and or cause air drafts either of which can interfere with pilot or burn...

Страница 8: ...liances CAN CGA 6 16 and a quick disconnect device that complies with the Standard for Quick Disconnect Devices for Use With Gas Fuel ANSI Z21 41 or Quick Disconnect Devices for Use with Gas Fuel CAN1 6 9 and adequate means must be provided to limit the movement of the appliance without depending on the connector and the quick disconnect device or its associated piping to limit the appliance movem...

Страница 9: ...several times until the new lines are purged of any trapped air and constant gas flow is attained Shut Down 1 Turn top burner valves clockwise to OFF position 2 When shutting down for periods longer than overnight turn the manual ON OFF valve on the incoming service line OFF Close all pilot adjusting screws right hand turn all the way in Final Preparation New units are wiped clean with solvent at ...

Страница 10: ...ast the radiants is connected by a second pan covering the reminder of the broiler bottom The front tray must be checked frequently during operation and drained as necessary the rear drip pan should also be checked occasionally Spills should be wiped as they occur and at the end of the day both pans should be washed in hot soapy water Periodic Your Garland Char Broiler should be checked and adjust...

Страница 11: ...Part 9229077 07 05 Page 11 NOTES ...

Страница 12: ......

Отзывы: