Model XMX Demand Expander 

 

Page 4 

 

©Copyright 2005-2013 

 

Gardner Denver Corporation 

Version 4.10

 

 

 

 

Left to Right configuration shown above.  Right to Left configuration is also available 

 

Since the controller has a built in by-pass, the unit can be simply placed in-line with no valving 

requirements by the installer.  

 

It  is  highly  recommended  that  an  automatic  drain  trap  be  placed  on  the  outlet  side  controller 

header  at  the  point  designated  as  “Drain”.    A  trap  on  the  inlet  header  can  be  used  as  well  if 

desired.    Place  the  factory  provided  pressure  gauges  on  the  inlet  and  outlet  headers  at  the 

indicated points. 

 

Prior  to  pressurizing  the  unit,  close  all  valves.    Once  pressure  has  been  applied,  and  prior  to 

applying power, slowly open valve V1.  The control valve is normally opened.  Slowly open valve 

V2, allowing air to flow from supply to demand side without control.  Valve V3 (by-pass) should 

now be opened and remain opened during the power up and initial tuning stages. 

 

Wiring (Stand-Alone with XMX-1V Controller):   

 

The controller requires a low current 115VAC supply, 2 amps. min. and two shielded and twisted 

pairs  of  wires  to  the  control  valve  and  pressure  transmitter  located  on  the  Demand  Expander 

assembly. Terminals L1 and L2 have been designated as the power input terminals and by using 

the provided conduit opening, place the 115 VAC hot wire on L1 and the neutral on L2.  Close the 

cabinet door and apply the power.  The display should be illuminated. 

 

 

 

 

115 VAC  POWER

L1

L2

 

 

 

 

Figure 1 - Connect 115 VAC Power to Terminals L1 & L2 

Содержание XMX Series

Страница 1: ...XMX Series Version 4 10 Demand Expander INSTALLATION INSTRUCTION MAINTENANCE MANUAL Gardner Denver Inc 1800 Gardner Expressway Quincy IL 62305 217 222 5400...

Страница 2: ...lators 5 Electronic Controller 6 P3 Storage Pressure 6 P4 System Pressure 6 Valve Control 6 Navigating through the LC Display 7 ESC 7 CURSER 7 OK 7 Setting the Pressure Set Point 7 PID Tuning 8 Propor...

Страница 3: ...n the supply side in the air receivers Eliminates artificial demand by lowering the flow through all leaks and unregulated points of use E Maintains a constant system pressure thus improving the quali...

Страница 4: ...ves Once pressure has been applied and prior to applying power slowly open valve V1 The control valve is normally opened Slowly open valve V2 allowing air to flow from supply to demand side without co...

Страница 5: ...eters need to be entered into the controller The following steps are necessary to achieve the above Setting the Regulators There is an air pressure regulator mounted and pre piped on the assembly It i...

Страница 6: ...e Terminals A1 and A1 Used only when connected by Ethernet to the ESP 20 20 Series 1000 controller and provides the storage pressure upstream of the Demand Expander to the master controller This is no...

Страница 7: ...menu to select USER DISPL The main screen indicating the P4 pressure and valve position will be displayed CURSER The diamond shaped curser control button in the middle will be used to advance numerica...

Страница 8: ...llating or not maintaining set point this value can be adjusted up or down by using the curser key Generally this will be moved lower if the valve control is erratic Proportional Set Point Screen Inte...

Страница 9: ...controller has an optional software routine that will provide forward pressure control with overriding back pressure protection The Demand Expander must be order with a normally closed valve Both P3 a...

Страница 10: ...e allowable on the high pressure side of the Demand Expander Press the OK button to advance to the next screen Downstream Set Point Screen The same method is used on the next screen to set the control...

Страница 11: ...made on the terminal strip in the Series 1000 controller as follows Connect the P3 Pressure Transmitter to terminals A1 and A1 in the Series 1000 controller Connect the P4 Pressure Transmitter to term...

Страница 12: ...t capability to properly setup a demand expander A real time trend appears on the Trending Page to assist with this tuning indicating the supply pressure which will be responding to the compressor con...

Страница 13: ...n be useful in processes with long time constants such as temperature control Too much derivative can make loops unstable Use with caution Expander Alarm Below Setpoint P4 is an offset subtracted from...

Страница 14: ...t point control Periodically the regulator settings should be checked for their accuracy Refer to section 3 0 A for proper setpoints and adjustments Should the valve require removal for replacement or...

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...I P MODULE VRC...

Страница 25: ......

Страница 26: ...VRC I P MODULE...

Страница 27: ...VRC...

Страница 28: ......

Страница 29: ...VRC...

Страница 30: ...VRC VRC VRC...

Страница 31: ......

Страница 32: ......

Страница 33: ...d proposed manner Gardner Denver does not warrant design details nor specific components requested by the customer and incorporated on the final design Any OEM equipment that does not perform to publi...

Страница 34: ...Gardner Denver Compressor Division ESP Series 1000 Controller Gardner Denver Inc 1800 Gardner Expressway Quincy IL 62305 217 222 5400...

Отзывы: