Derivative- 

By pressing OK, the value is accepted and the screen advances to the DERIVATIVE set display.  

It is not recommended that the derivative value is set to any value above zero.  If the system has 

wide swings in demand and the valve is not keeping up, the derivative function biases the control 

based on the rate of pressure change.  It can be increased slowly in order to assist with valve 

control.  This is very rare however. 

 

 

 

 

 

 

 

 

 

Derivative Set Point Screen 

 

When the OK button is again pushed, the screen will return to the overview display providing the 

actual system pressure and valve position.  The system is ready for operation. 

 

Optional Back Pressure Control: 

 

The standard controller has an optional software routine that will provide forward pressure control 

with overriding back pressure protection.  The Demand Expander must be order with a normally 

closed  valve.  Both  P3  and  P4  pressures  must  be  connected  and  set  points  for  both  forward 

pressure  and  back  pressure  must  be  entered.    When  selected,  by  the  installation  of  a  jumper 

b24 VDC and I/1 on the processor’s input terminals, the software automatically adjusts 

and the screen navigation reflects the added set point entry requirements and pressure displays.  

 

Pressure will alternate between P3 and P4 pressure on the overview display and valve position 

will reflect the actual valve output signal in percent. 

 

 

  

 

 

 

 

 

 

 

 

Alternating Overview Screens 

 

The main overview screen will alternate between the P3 and P4 pressure readings and provide 

the valve position as calculated by the controller. 

REMOTE

XMX DEM EXP

DERIVATIVE

=                   0

REMOTE 

XMX DEM EXP 

P3 PRESS = 85 

VALVE % = 92 

REMOTE 

XMX DEM EXP 

P4 PRESS = 92 

VALVE % = 92 

Содержание XMX Series

Страница 1: ...XMX Series Version 4 10 Demand Expander INSTALLATION INSTRUCTION MAINTENANCE MANUAL Gardner Denver Inc 1800 Gardner Expressway Quincy IL 62305 217 222 5400...

Страница 2: ...lators 5 Electronic Controller 6 P3 Storage Pressure 6 P4 System Pressure 6 Valve Control 6 Navigating through the LC Display 7 ESC 7 CURSER 7 OK 7 Setting the Pressure Set Point 7 PID Tuning 8 Propor...

Страница 3: ...n the supply side in the air receivers Eliminates artificial demand by lowering the flow through all leaks and unregulated points of use E Maintains a constant system pressure thus improving the quali...

Страница 4: ...ves Once pressure has been applied and prior to applying power slowly open valve V1 The control valve is normally opened Slowly open valve V2 allowing air to flow from supply to demand side without co...

Страница 5: ...eters need to be entered into the controller The following steps are necessary to achieve the above Setting the Regulators There is an air pressure regulator mounted and pre piped on the assembly It i...

Страница 6: ...e Terminals A1 and A1 Used only when connected by Ethernet to the ESP 20 20 Series 1000 controller and provides the storage pressure upstream of the Demand Expander to the master controller This is no...

Страница 7: ...menu to select USER DISPL The main screen indicating the P4 pressure and valve position will be displayed CURSER The diamond shaped curser control button in the middle will be used to advance numerica...

Страница 8: ...llating or not maintaining set point this value can be adjusted up or down by using the curser key Generally this will be moved lower if the valve control is erratic Proportional Set Point Screen Inte...

Страница 9: ...controller has an optional software routine that will provide forward pressure control with overriding back pressure protection The Demand Expander must be order with a normally closed valve Both P3 a...

Страница 10: ...e allowable on the high pressure side of the Demand Expander Press the OK button to advance to the next screen Downstream Set Point Screen The same method is used on the next screen to set the control...

Страница 11: ...made on the terminal strip in the Series 1000 controller as follows Connect the P3 Pressure Transmitter to terminals A1 and A1 in the Series 1000 controller Connect the P4 Pressure Transmitter to term...

Страница 12: ...t capability to properly setup a demand expander A real time trend appears on the Trending Page to assist with this tuning indicating the supply pressure which will be responding to the compressor con...

Страница 13: ...n be useful in processes with long time constants such as temperature control Too much derivative can make loops unstable Use with caution Expander Alarm Below Setpoint P4 is an offset subtracted from...

Страница 14: ...t point control Periodically the regulator settings should be checked for their accuracy Refer to section 3 0 A for proper setpoints and adjustments Should the valve require removal for replacement or...

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...I P MODULE VRC...

Страница 25: ......

Страница 26: ...VRC I P MODULE...

Страница 27: ...VRC...

Страница 28: ......

Страница 29: ...VRC...

Страница 30: ...VRC VRC VRC...

Страница 31: ......

Страница 32: ......

Страница 33: ...d proposed manner Gardner Denver does not warrant design details nor specific components requested by the customer and incorporated on the final design Any OEM equipment that does not perform to publi...

Страница 34: ...Gardner Denver Compressor Division ESP Series 1000 Controller Gardner Denver Inc 1800 Gardner Expressway Quincy IL 62305 217 222 5400...

Отзывы: