background image

10

TROUBLESHOOTING GUIDE

SYMPTOM

A.

Water downstream of dryer

B.

High pressure drop across
dryer

C.

Dew point indicator in red
area

D.

Refrigeration system not
functioning properly

1.

Compressor on light off

     2.

Refrigerant compressor
cycles on and off

POSSIBLE CAUSE(S)

1. Residual free moisture remaining

in downstream pipelines

2. Air by-pass system is open
3. Inlet and Outlet connections are

reversed

4. Temperatures surrounding air

lines downstream of dryer have
dropped below dryers dew point
rating

5. Excessive free moisture (bulk

liquid) at dryer inlet

6. Condensate not being automati-

cally drained
Drain mechanism is clogged or
inoperative.
Drain line is restricted or frozen.
Electric drains–timer not set to
allow for sufficient condensate
removal

7. Dryer overloaded resulting in

elevated dew point.

8. Refrigeration system not func-

tioning properly resulting in
elevated dew point.

1. Excessive air flow
2. Freezing of moisture in evapora-

tor because of refrigeration
system improperly functioning.

3. Separator or optional Oil Removal

filter element clogged.

1. Dryer overloaded resulting in high

air outlet temperature.

2. Refrigeration system not func-

tioning properly resulting in high
air outlet temperature.

3. Dryer is running with no load

a. Power failure
b. Line disconnect switch open
c. Blown fuses, open breaker
d. Faulty wiring, loose terminals

a. High or low ambient conditions
b. Air-cooled models–Dirty, clogged

condenser fins, obstructed air
flow across condenser, or non
functioning fan motor or fan
control switch.

CORRECTIVE ACTION

Blow out system with dry air

Check valve positions
Check for correct connection

Insulate or heat trace air lines exposed to
low ambients or dry air to lower dew point

Install separator ahead of dryer

Replace drain mechanism if inoperative

Open drain line
Electric drains–reset time so that all liquid
is discharged

Check inlet air temperature and pressure,
flow rate (compressor capacity) and
ambient air or water temperature.
See D below

Check flow rate
See D below

Replace filter element(s).

See A 7

See D below

Light will go out when air flow is estab-
lished

Check power to unit
Close disconnect switch
Check for continuity
Have electrician check electrical
connections
Check min./max.  temperature ranges
Clean condenser and check for free air
flow, if problem persists contact qualified
refrigeration repairman or manufacturer’s
service department.

Содержание RNC25

Страница 1: ...DELS RNC25 RNC35 RNC50 RNC75 RNC100 CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 4 3 0 MAINTENANCE 6 SIZING 6 ENGINEERING DATA 7 ELECTRICAL SCHEM...

Страница 2: ...evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the delivery receipt by the carrier s agent B UNPACKING Check for Concealed Loss or Dama...

Страница 3: ...r installation Standard units are designed for indoor installation Contact manufacturer if installing outdoors 1 2 Mounting Mount the dryer on a level solid surface Holes are provided in the dryer bas...

Страница 4: ...ranty 1 5 Moisture separator A Separator and Oil Removal Filter where applicable has an internal drain which automatically discharges collected condensate It may be desirable to pipe the condensate fr...

Страница 5: ...2 Where the dryer is consistently operating at less than maximum capacity it may be possible to increase the LED set point to minimize air loss Discretionary adjustments to the dryer should only be m...

Страница 6: ...d drain mechanism annually To facilitate service maintenance kits are available Please refer to page 11 3 0 Maintenance Sizing Determining dryer capacity at actual operating conditions To determine th...

Страница 7: ...29 220 183 350 292 Electrical Nominal Voltages 115 1 60 Max Min Voltage 127 104 127 104 127 104 127 104 127 104 Rated Load Amps 3 4 3 9 5 9 7 4 10 3 Locked Rotor Amps 18 0 22 0 28 0 35 0 48 0 Minimum...

Страница 8: ...load TB Terminal Block CAP Start Capacitor SR Start Relay DRN1 Drain Solenoid STD IC2 MTR Compressor DRN2 Drain Solenoid IC2 Oil Coalescing Option FM Fan Motor TC1 Temperature Sensor Optional Notes 1...

Страница 9: ...G 18 3 16 18 3 16 18 3 16 20 11 16 20 11 16 H 21 3 16 21 3 16 21 3 16 24 3 16 24 3 16 I 18 1 2 18 1 2 18 1 2 24 24 J 16 1 2 16 1 2 16 1 2 21 13 16 21 13 16 Inlet Outlet Connections 1 2 MPT 1 2 MPT 1 2...

Страница 10: ...gh air outlet temperature 2 Refrigeration system not func tioning properly resulting in high air outlet temperature 3 Dryer is running with no load a Power failure b Line disconnect switch open c Blow...

Страница 11: ...0 120 5 G4130 120 8 G4130 120 9 G4130 121 11 G4130 121 9 G4130 121 9 G4130 122 10 G4130 122 11 G4130 122 15 Compressor Only G4130 108 34 G4130 108 61 G4130 108 35 G4130 108 38 G4130 108 39 G4130 108 4...

Страница 12: ...T OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE TO DISCOVER REPORT REPAIR OR MODIFY LATENT DEFECTS INHERENT THEREIN THE MANUFACTURER H...

Отзывы: