13-11-607 Page 22
7. In the top line, “
REMOTE STOP
” is displayed. The bottom line indicates either “TIMED” or
“IMMEDIATE”. Refer to the description of “Remote On/Off” later in this section for additional details.
Select the desired response to the remote input and press [ENTER] to proceed.
8. This completes the operational adjustments. The controller will return to the main adjustments menu.
Maintenance Adjustments
1.
If any service advisories are in effect (yellow ADVISORY indicator is on), they will be displayed on
the top line. The bottom line indicates “
LEAVE ADVISORY
” (do not reset) or “
CLEAR ADVISORY
”
(turn it off). Select the desired action and press [ENTER] to proceed.
2.
The top line displays “
NEXT RELUBE
” and the hours remaining are displayed on the bottom line.
Press the [+] or [-] keys to switch to the lubrication change interval (see UNIT SETUP) if service was
performed early. Press [ENTER] to proceed.
3.
This completes the maintenance adjustments. The controller will return to the main adjustments
menu.
Sequence Adjustments
See “SEQUENCING COMPRESSORS WITH THE AUTO SENTRY W, page 24
,
for more details on
setting up and optimizing a sequenced compressor installation.
1.
In the top line, “
NUM OF SEQ UNITS
” is displayed. The bottom line will indicate a number in the
range of one through eight. This will be factory set at “1”. This should be set to a number
corresponding to the number of compressors that are currently installed on this air system that also
have AUTO SENTRY W controllers. It should be noted that all AUTO SENTRY W compressors on
the system must have the same number programmed here to operate correctly in SEQUENCE
mode. Adjust as required, and press [ENTER] to proceed.
NOTICE
Setting the value in Step 1 to one indicates that no sequencing is to take place.
Consequently, Steps 2, 3 & 4, which relate to sequencing, are skipped by the
AUTO SENTRY W; the controller will return to the main adjustments menu.
2.
In the top line, “
UNIT NUMBER
” is displayed. The bottom line will again indicate a number of one
through eight and be factory set at “1”. Each AUTO SENTRY W in a sequenced system must have
a unique number here. The sequence mode will not function if two or more compressors have the
same UNIT NUMBER. The most efficient machine-to-machine communications will occur when the
lowest possible numbers are used. Example: 1, 2, and 3 for a three compressor installation.
All other settings should normally be the same for all units.
3.
In the top line, “
TRANSFER INTERVAL
” is displayed. The bottom line will indicate a number of
hours in the range of 1 to 5000. It is factory set at 24. This is the number of hours that this machine
will stay in the role of “master” or ”lead” compressor.
Normally it is desirable to set this to the same value on all sequenced units to equalize running
hours. Different values may be programmed, if desired, to help equalize hours.
Содержание PUREAIR EWC99C
Страница 7: ...13 11 607 Page 2 Figure 1 2 PACKAGE ILLUSTRATION 307EWC797 B Ref Drawing...
Страница 8: ...13 11 607 Page 3 Figure 1 3 AIR WATER SCHEMATIC 308EWC797 F Ref Drawing...
Страница 25: ...13 11 607 Page 20 Figure 4 2 FLOW CHART FOR SETUP PROGRAMMING 300EWC1255 Ref Drawing...
Страница 38: ...13 11 607 Page 33 Figure 4 4 WIRING DIAGRAM FULL VOLTAGE 305EWC546 B Ref Drawing Page 1 of 2...
Страница 39: ...13 11 607 Page 34 305EWC546 B Ref Drawing Page 2 of 2...
Страница 40: ...13 11 607 Page 35 Figure 4 5 WIRING DIAGRAM FULL VOLTAGE LESS STARTER 306EWC546 B Ref Drawing Page 1 of 2...
Страница 41: ...13 11 607 Page 36 306EWC546 B Ref Drawing Page 2 of 2...