13-17-621 Page 14
Operating conditions
Installation elevation above sea level
0 to 2000 m
No limitation
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
Ambient Conditions
Temperature
Operation
-20 to 60°C
Storage
-25 to 70°C
Transport
-25 to 70°C
Relative humidity
5 to 95%, non-condensing
Mechanical Properties
Front
Keypad overlay
Material
Polyester
Design
Customized
Dimensions
Width
197 mm
Height
140 mm
Depth
47.8 mm
weight
0.6 kg
2.3.1.2 Diagnostics LEDs:
The diagnostic LEDs are located on the back of the Power Panel. Figure 6 below displays the diagnostic
LEDs available on the Display Module.
Figure 6: LEDs in Display Module
Table 2 below explains the LEDs and their Color Codes.
Table 2: Display Module LED Diagnostic
LED STATUS
LED
Color
Status
Description
RDY/F
Yellow
On
Mode BOOT, SERVICE or DIAGNOSIS
Blinking
LED "R/E" blinks red and LED "RDY/F" blinks yellow, when there is a
license violation.
R/E
Green
On
Mode RUN: The application is running.
Red
On
Mode BOOT, SERVICE or DIAGNOSIS
Blinking
LED "R/E" blinks red and LED "RDY/F" blinks yellow when there is a
license violation.
CAN (IF4)
Yellow
On
Data is transmitted via CAN bus interface IF4.
TERM (IF4)
Yellow
On
The integrated terminating resistor for the CAN bus interface (IF4) is
switched on.
RS485 (IF5)
Yellow
On
Data is transmitted via CAN bus interface IF6.
TERM (IF5)
Yellow
On
The integrated terminating resistor for the RS485 bus interface (IF5) is
turned on.
Содержание Governor TEN014983
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally...