
13-17-621 Page 35
o
If the pressure is below the load pressure setting, it will be displayed in blue:
o
If the pressure is above the Load pressure and less than the Warning pressure setting, it
will be displayed in green:
o
If the pressure is between the Warning and Fault pressure settings, it will be displayed in
yellow:
o
If the pressure is above the Fault pressure setting, it will be displayed in red:
2. The Discharge Temperature gauge shows the compressor airend discharge temperature.
o
If the temperature is below the Minimum Start Temperature setting, it will be displayed in
red.
o
If the temperature is between the Minimum Start Temperature setting and 3
℃
(5.4
℉
)
above the Minimum Start Temperature, it will be displayed in yellow.
o
If the temperature is above the Minimum Start Temperature plus 3
℃
(5.4
℉
) and below the
Warning temperature setting, it will be displayed in green.
o
If the temperature is above the Warning temperature setting and below the Fault
temperature setting, it will be displayed in yellow.
o
If the temperature is above the Fault temperature setting, it will be displayed in red.
Содержание Governor TEN014983
Страница 12: ...13 17 621 Page 12 Figure 4 Oblique View Figure 5 Rear View...
Страница 165: ...13 17 621 Page 165 Figure 176 Sequencing Diagnostics ES Protocol Figure 177 Sequencing Diagnostics AirSmart Protocol...
Страница 188: ...13 17 621 Page 188 Figure 217 VFD Diagnostics Figure 218 VFD Diagnostics...
Страница 193: ...13 17 621 Page 193 Page left blank intentionally...