13–8–610 Page 24
Load setpoint cannot be set within 8 psi (.6 Bar) of the unload
setpoint.
Minimum operating pressure is 60 to 65 PSIG (4.1 to 4.5 Bars).
NAMEPLATE CONTROL SYSTEM PRESSURE
FULL LOAD
OPERATING PRESSURE
LOAD
UNLOAD
100 PSI (6.9 Bars)
100 PSI (6.9 Bars)
108 PSI (7.5 Bars)
125 PSI (8.6 Bars)
125 PSI (8.6 Bars)
133 PSI (9.2 Bars)
150 PSI (10.4 Bars)
150 PSI (10.4 Bars)
158 PSI (10.9 Bars)
175 PSI (12.1) Bars)
167 PSI (11.5 Bars)
175 PSI (12.1 Bars)
FIGURE 4–8 – MAXIMUM SETPOINTS FOR AUTO SENTRY “S” CONTROLLER, PSIG
FIGURE 4–9 – AUTO SENTRY “S” SOLID STATE CONTROL TOUCH PAD
Содержание ELECTRA-SCREW EDEQHH
Страница 10: ...13 8 610 Page 2 200EDE797 Ref Drawing FIGURE 1 2 PACKAGE MINIMUM PRESSURE CHECK VALVE MIXING VALVE OIL FILTER...
Страница 11: ...13 8 610 Page 3 200EDE797 Ref Drawing FIGURE 1 3 PACKAGE OIL LEVEL GAUGE SEPARATOR AIR FILTER...
Страница 12: ...13 8 610 Page 4 202EDE797 Ref Drawing FIGURE 1 4 PACKAGE CONTROLLER STARTER BOX...
Страница 15: ...13 8 610 Page 7 DECALS 206EAQ077 212EAQ077 218EAQ077 211EAQ077 207EAQ077...
Страница 16: ...13 8 610 Page 8 DECALS 216EAQ077 217EAQ077 222EAQ077 221EAQ077 208EAQ077...
Страница 33: ...13 8 610 Page 25 FIGURE 4 10 WIRING DIAGRAM FULL VOLTAGE DUAL CONTROL 204EDE546 Ref Drawing...
Страница 34: ...13 8 610 Page 26 FIGURE 4 11 WIRING DIAGRAM WYE DELTA 205EDE546 Ref Drawing...