24
b
Output current 2
c
Output current 3
d
Output current 4
e
Maximum current rating of LEDs
p
Pulse width (ms)
del
Delay before pulse (ms)
The 3
rd
line is for factory use
The 4
th
and 5
th
lines are the debounce period for each input
T
i
D
d
Where:
I
Input channel (1 or 2)
D
Debounce period (ms)
Example of Reading Settings
If output channel 1 is set up for four currents of 0.25mA, 25.7mA, 0.5A,
1.5A, selected using combinations of inputs 1 and 2 and output channel 2
set up to pulse a current of 5.35A for 100ms, using input 1 as trigger and
a delay of 15ms, with a debounce period of 20ms. The result of the ST
command will be:
01 M 06 E 1000 V 0.2, 25.7, 500, 1500,
02 M 01 E 7000 V5350.0 D 15.0 P 0.10
P1 M 00 U
T01 D 20.00
T02 D 0.00
GR
Clears error display from LEDs.
Syntax:
GR
This command has 4 possible responses.
Responses:
>
No overcurrent operation
EC1
Channel 1 has been over current since last GR
EC2
Channel 2 has been over current since last GR
ET
The PP600 has overheated and has switched off both
outputs
EC1EC2 Both channels have been over current since last GR
ET response was introduced in firmware revision 017.
VR
Report the version of firmware running in the PP610
Syntax:
VR
Response:
version