Enhanced Electronic Governor EEG7000 with GAConfig Tool 8-2021-D6
PIB1009
GAC
onfig
- SETTING All PARAmETERS (CONTINUED)
14
Quick Configuration - Advanced Configuration
Parameter
min - max
DefaUlt noteS
I/O Configuration - Speed Switch Output
Communication Mode CAN or RS232
Sets the controller to use CAN or RS-232 communication.
SSW Limit
100 - 6000 rpm
1800
Speed limit for speed switch 1 output.
Latching
Select -
Deselect
Select
Selecting Latching sets the output state ON until power is cycled. With the Latch setting
deselected, the output state of the pin automatically resets at 0 rpm.
SSW Mode
Normally Open,
Normally Closed
Normally
Open
Mode sets the output polarity at either normally open or normally closed.
aux / load Sharing
Auxiliary Enable
Select - Deselect
Deselect
Selects if the auxiliary / load sharing function is used.
Auxiliary Polarity
Decreasing Speed,
Increasing Speed
Decreasing
Speed
Auxiliary Polarity either increases speed with increased voltage or decreases speed with
increased voltage. Auxiliary Polarity is nominally 5.0 V +/- 5.0 V DC.
Droop
No Load Current
0 - 5.5 A
0.5 A
Actuator current at rated speed, no load.
Full Load Current
0.5 - 6.0 A
6.0 A
Actuator current at rated speed, full load.
Fixed Speed 1, 2, 3,
Droop
0 - 25 %
0
Percent of droop (% rpm decrease at full load) to incorporate while in fixed speed select
1, 2, or 3.
Variable Speed Droop 0 - 25 %
0
Percent of droop (% rpm decrease at full load) to incorporate while in variable speed
mode.
SAE J1939 Configuration
J1939 Address
0 - 253
0
Sets the CAN address for J1939 communication
Engine Requested
Torque / Speed
0 - 6000 rpm
1500
The value the controller is being requested to govern at through the J1939 TSC1 com-
mand
Engine Override
Control Mode
Disabled-Enabled
Disabled
Currently unavailable. Will control PGN0 SPN695 Current Torque/Speed Control 1 - En-
gine Override Control Mode.
Speed Ramping
Select - Deselect
Deselect
Current TSC1 speed command limit
J1939 Diagnostic
Messages (DM)
---
---
DM1 and DM2 status and reset
System & Status information - run time meters
Engine Runtime
h
Hours
Service Timer Enable Disabled-Enabled
Disabled
Controls the service timer. *Transitioning from disabled to enabled automatically sets the
service timer to +500 hours
Current Service
Hours
1 - 2000
500
Setting service hours sets the hour meter for an alert at the selected service interval. If
the service time is expired, the displayed number will be ‘0’ or negative.
Reset Service Hours
1 - 2000
500
When the service timer is enabled, resets the service counter to this value
Engine Runtime
0 - 65535.9
Current runtime hours
System commands
System Reset
--
Performs a software reset of the system. Engine speed must be 0.
Engine Shutdown
Button
Software commanded engine shutdown.
Factory Restore
Button
Restores GAC factory default settings to GAConfig Tool and the EEG7000 controller. It
does not reset to OEM default settings.
System Status and System Configuration
Battery Voltage
Current battery reading.
Fault Information
System Configuration
Information
Hardware and software information for EEG7000 and GAConfig Tool
Items in Gray are display only.