background image

 

D1033 

- SIL 2 Switch / Proximity Detector Repeater Transistor Output 

G.M. International ISM0043-15 

Front Panel and Features 

Ordering information 

Model:   D1033 

2 channels 

Common negative and positive 

4 channels 

-052 

 

 

Common negative only 

Common positive only 

Power Bus enclosure 

blank 

-058 

/B 

 

 



SIL 2 according to IEC 61508:2010 Ed.2 for Tproof = 6 / 10 years (

10% / >10 % of total SIF). 



PFDavg (1 year) 1.54 E-04, SFF 75.41 %. 



SIL 3 Systematic capability 



Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2. 



NO/NC contact/proximity Detector Input. 



Four opto isolated voltage free transistor Output Signals. 



Common negative or positive output both accepted in standard version D1033. 



Transistor Output for fault detection on dual channel version. 



Line fault detection with common signalling available when using Power Bus enclosure. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1. 



In-field programmability by DIP Switch. 



ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, TÜV Certifications. 



TÜV Functional Safety Certification. 



Type Approval Certificate DNV and KR for maritime applications. 



High Reliability, SMD components. 



High Density, four channels per unit. 



Simplified installation using standard DIN Rail and plug-in terminal blocks. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

Power Bus and DIN-Rail accessories: 
DIN rail anchor MCHP065    DIN rail stopper MOR016 
Terminal block male MOR017  Terminal block female MOR022 

Содержание D1033Q

Страница 1: ...033 SIL 2 Switch Proximity Detector Repeater Transistor Output ISM0043 15 D1033D D1033Q INSTRUCTION SAFETY MANUAL SIL 2 Switch Proximity Detector Repeater Transistor Output DIN Rail Models D1033D D103...

Страница 2: ...ms to 7113 22782 5 78 I 60079 15 T V Certificate No C IS 236198 03 SIL 2 conforms to IEC61508 2010 Ed 2 T V Certificate No C IS 236198 09 SIL 3 Functional Safety Certificate conforms to IEC61508 2010...

Страница 3: ...d in standard version D1033 Transistor Output for fault detection on dual channel version Line fault detection with common signalling available when using Power Bus enclosure Three port isolation Inpu...

Страница 4: ...Voltage free Contact Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact Input Ch 2 for Proximity Input Ch 2 for Voltage free Contact Input Ch 2 for Proximity Input Ch 2 for Voltage free C...

Страница 5: ...iated Apparatus excluding the cable then 50 of Co and Lo parameters are applicable and shall not be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C ca...

Страница 6: ...N HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1033Q 13 14 3 4 1 2 Common Channels 1 3 Supply 24 Vdc Out 1 5 6 Common Channels 2 4 Out 2 7 Out 3 8...

Страница 7: ...fety Function dd du sd su 142 61 MTBF safety function one channel 1 tot safe MTTR 8 hours 800 years no effect No Effect failures 116 69 not part Not Part failures 218 50 tot device Total Failure Rate...

Страница 8: ...rs no effect No Effect failures 127 75 not part Not Part failures 370 70 tot device Total Failure Rate Device tot safe no effect not part 645 40 MTBF device one channel 1 tot device MTTR 8 hours 176 y...

Страница 9: ...s or Hazardous Classified Locations Class I Division 2 Groups A B C D T Code T4 Class I Zone 2 Group IIC IIB IIA T Code T4 FM Approved under Entity Concept or third party approval Hazardous Classified...

Страница 10: ...ed from each other and do not produce any unintentional connection Connect SPST output transistors checking the load rating to be within the maximum rating 100 mA 35 V resistive load The enclosure pro...

Страница 11: ...with terminating line resistor ON CH2 Setting Line fault detection ON IN OUT Operation NO NC or NC NO NO NO or NC NC ON OFF Disabled contact proximity sensor Enabled proximity sensor or contact with t...

Страница 12: ...Output Input Output Output Input Output Input 9 NO 10 OR NC 9 10 9 NO 10 OR NC 9 10 7 NO 2 NC 7 2 7 NO 2 NC 7 2 Input Output Input Output Output Input Output Input 11 NO 12 OR NC 11 12 11 NO 12 OR NC...

Страница 13: ...ut Input Output Output Input Output Input 13 NO 14 OR NC 13 14 13 NO 14 OR NC 13 14 1 ND 2 NE 1 2 1 ND 2 NE 1 2 ND Mode NC Mode No Fault No Fault 7 ND 2 NC 7 2 Switch 4 positions Input Output Input Ou...

Страница 14: ...utput Input Output 15 NO 16 NC 15 16 8 NC 6 NO 8 6 Switch 8 positions Input Output Input Output 15 NO 16 OR NC 15 16 8 NO 6 NC 8 6 ON Switch 8 positions OFF Switch 8 positions OR Switch 4 positions Sw...

Отзывы: