Carbon Filter Start Up Procedure 

The water filter should be installed with the inlet, outlet, and drain connections made in 
accordance with the manufacturer's recommendations, and to meet applicable plumbing 
codes. 

1.  Push and hold the “extra cycle” button (far left button with triangle shaped arrows on the but-

ton).  This button will advance the valve to the next cycle if it is pushed and released. 

2.  This will position the valve to backwash. You will see BW and four dashes.  The four dashes 

will change to a time value that will start to count down.  Once the time begins to count 
down.  Slowly open the bypass valve to the service position.  Ensure the drain line flow re-
mains steady for 10 minutes or until the water runs clear. 

3.  After the backwash cycle, the valve will move to the rapid rinse position. Check the drain line 

flow, and run for 5-10 minutes or until the water runs clear. 

4.  The filter is now installed.   
 

H2O2 Injection Setting 

 
US Water Systems uses the “bubble method”.  This is a visual method that works best for quick 
and reliable H2O2 injection rates. 
 
1.  Set the proportional control on the Stenner injection panel (gray wall mount panel) to 40% 

(there is a dial on the little black box (PCM) that the pump is plugged in to).   

2.  Run water for 10-15 minutes.   
3.  Take a sample after the carbon tank (or at a sink).  The water in the sample container 

(preferably glass) should be full of bubbles immediately after the sample is taken.  If not the 
installer will adjust the knob to 50%, run the water for 10-15 minutes and check again.   

4.  Continue adjusting the knob up in increments of 10% until the sample container is full of bub-

bles.  Once the container is full of bubbles, it is an indicator that there is plenty of H2O2 in 
the water.   

5.  Continue the same process decreasing the knob setting in 5% increments allowing the water 

to run for 10-15 minutes between adjustments until there are just a few bubbles in the sam-
ple container (20-30 defined air bubbles) that come to the top of the water level and dissipate 
immediately.  This should be the optimal H2O2 injection setting. 

 
This is an indicator that there is a small amount of residual H2O2 in the treated water and the contaminant 
is being oxidized.  Once this setting is determined the system will operate automatically.   
 
Over the first 1-3 months it is important to monitor the H2O2 level in the storage/solution tank and start to 
gain usage data that will help you determine the H2O2 usage and allow you to plan/order replenishment 
H2O2 accordingly.    This setting should be periodically checked and adjusted due to changes in the aqui-
fer (well) and loss of H2O2 concentration by degradation.   After 6-8 months the H2O2 can lose concentra-
tion, so only replenish the tank to a level that can be used in 6-8 months to ensure the H2O2 concentration 
strength is consistent.   

 

Installation, Operation and Maintenance Manual 

Oxi-Gen Oxi-2P,3P,4P, 5P & 6P System 

Содержание Oxi-Gen 150-OXi-2P

Страница 1: ...on Sulfur and Manganese Eradication System Oxi Gen 150 OXi 2P Oxi Gen 150 OXi 3P Oxi Gen 150 OXi 4P Oxi Gen 150 OXi 5P Oxi Gen 150 OXi 6P US Water Systems Inc 1209 Country Club Road Indianapolis IN 46...

Страница 2: ...and Valve Installation 8 Carbon Filter Installation Instructions 9 Carbon Filter Valve Features 10 Carbon Filter Valve Features and Programming 12 Carbon Filter Valve Programming 13 Carbon Filter Sta...

Страница 3: ...er of bathrooms 1 Bathroom 5 GPM 2 Bathrooms 8 GPM 3 Bathrooms 10 GPM 4 Bathrooms 12 GPM 5 Bathrooms 15 GPM 6 Bathrooms 20 GPM Hydrogen peroxide or H2O2 is a powerful yet versatile oxidant that is bot...

Страница 4: ...e oxidizes the contaminants and the by product is H2O water This is much safer than using chlorine in that chlorine can cause other problems in the water stream such as chloramines and trihalomethanes...

Страница 5: ...to assure the accuracy of the dosage The Stenner Proportional Injection System can be utilized to inject any number of chemicals including chlorine hydrogen peroxide polyphosphate Rid O Rust and many...

Страница 6: ...5 Secure wall mount bracket to wall studs using the included lag bolts or other suitable hardware Hang panel on to wall mount bracket 6 Glue stubbed cut pipe into slip socket After glue is cured hand...

Страница 7: ...4 Slide roof into pump mounting bracket over motor WARNING When pressurizing the system gradually allow water to flow Shocking the meter by over speeding it with high flow rates can damage the interna...

Страница 8: ...stem 1 Remove the tank from carton 2 Verify the riser is still fully engaged in the Vortech plate 3 Place a piece of duct tape over the riser tube so no media enters the riser while filling 4 Make sur...

Страница 9: ...nimum of 1 2 Backwash flow rates in excess of 7 gpm or length in excess of 20 require 3 4 drain line Commercial drain lines should be the same size as the drain line flow control 4 The inlet on the by...

Страница 10: ...by pressing the Extra Cycle button for five seconds The Parameter Display displays the current Cycle Step BW RR etc during backwash and the data display counts down the time remaining for that cycle...

Страница 11: ...d backwash time when the number of days since the last backwash equals the backwash day override value Day of the Week Control This control regenerates the system on a weekly schedule The schedule is...

Страница 12: ...or do not appear in filter mode Entering Master Programming Mode Set the Time Of Day display to 12 01 P M Press the extra cycle Then press and hold the Up and Down buttons together until the programmi...

Страница 13: ...2 in Service C Unit Capacity Unit Capacity Grains H Feedwater Hardness Hardness of Inlet Water RS Reserve Selection Percentage Safety Factor rc Fixed Reserve Capacity SF Safety Factor Percentage of t...

Страница 14: ...preferably glass should be full of bubbles immediately after the sample is taken If not the installer will adjust the knob to 50 run the water for 10 15 minutes and check again 4 Continue adjusting th...

Страница 15: ...s an indication that the system is being overfed with H2O2 This occurs because after installation the water will become cleaner and the initial dosage of H2O2 may need to be adjusted to compensate for...

Страница 16: ...ter Open blow down valve and flush the filter 3 6 Months N A Injection Panel Pump Tube Inspect pump tube and replace as needed 2 Tube 1 5 Years 411 UCCP202 Injection Panel Duck Bill Check Valve Replac...

Страница 17: ...17 Flow Schematic Installation Operation and Maintenance Manual Oxi Gen Oxi 2P 3P 4P 5P 6P System...

Страница 18: ...ther casualty or if the original serial numbers have been removed Fouling or damage to the resin caused by iron sulfur bacterial iron silt sand tannins or ganics bacteria hot water or chlorine voids t...

Отзывы: