<Cooling operation>
OK
OK
OK
OK
OK
<Heating operation>
Compressor Temperature Thermistor
"Protection stop by "compressor temperature
compressor operation"" generated 2 times within 24 hours.
Test 1 : Check if 3-way valve(gas side) is open.
(Check by disconnecting thermistor from PCB.)
*
For the characteristics of the thermistor, refer to the "Trouble shooting 12".
Test 4 : Check the
thermistor Compressor
EEV open?
Strainer clogging check
Refer to “
SERVICE PARTS INFORMATION 3
”
Refer to “
SERVICE PARTS INFORMATION 3
”
Test 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (
SERVICE PARTS INFORMATION 5
)
Test 2 : Check the EEV, strainer
Test 5 : Check the refrigerant amount
Leak check
EEV open?
Strainer clogging check
Test 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
Test 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
Trouble shooting 22
OUTDOOR UNIT Error Method:
Compressor Temp. Error
1. 3-way valve not opened 2. EEV defective, strainer clogged
3. Outdoor unit operation failure, foreign matter on heat exchanger
4. Compressor temperature thermistor failure
5. Insufficient refrigerant
6. Main PCB failure
226.4°F (108°C) during
Compressor thermistor characteristics check
02-24
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 10 times Flash, Timer lamp: 3 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : A3]
Detective Actuators:
Detective details:
Forecast of Cause:
Содержание R410A
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...