Trouble shooting 8
INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Test 1 : Check rotation of Fan
Test 2 : Check ambient temp. around motor
OK
OK
OK
Indoor unit Controller PCB
Indoor unit Fan motor
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Control PCB failure 5. Indoor unit fan motor failure
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>> If Fan or Bearing is abnormal, replace it.
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
Test 4 : Replace Controller PCB
If Test 1- 3 do not improve the symptom, replace Controller PCB.
Test 3 : Check Indoor unit fan motor
Check Indoor unit fan motor.
(SERVICE PARTS INFORMATION 4)
>>If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
02-10
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 5 times Flash, Timer lamp: 1 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 51]
Detective Actuators:
Detective details:
Forecast of Cause:
Содержание R410A
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...