Trouble shooting 11
OUTDOOR UNIT Error Method:
OK
OK
18.1
26.9
20
41.1
64.5
81.8
104.6
134.9
175.7
Resistance value (k )
15
10
5
0
Temperature (°C )
12.5
30
50
40
60
2.0
3.4
4.6
6.3
8.8
Resistance value (k )
120
100
90
80
70
Temperature (°C )
Discharge Thermistor Error
Outdoor Unit Main PCB
Discharge Pipe Temperature Thermistor
When Discharge Pipe Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Main PCB failure
Test 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or miss-wiring, reset the power.
Test 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Test 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
Temperature (°F )
32
41
50
59
68
86
104
122
140
Temperature (°F )
158
176
194
212
248
CN64
CN62
1
2
1
2
3 3
1
2
1
2
3 3
BLUE
BLUE
BROWN
BROWN
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( COMPRESSOR TEMP. )
CN65
CN63
1
2
1
2
3 3
1
2
1
2
3 3
BROWN
BROWN
BLACK
BLACK
THERMISTOR
( DISCHARGE TEMP. )
THERMISTOR
( PIPE TEMP. )
02-13
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 7 times Flash, Timer lamp: 1 times Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 71]
Detective Actuators:
Detective details:
Forecast of Cause:
Содержание R410A
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...