THERMO CONTROL ( FOR INDOOR UNIT SENSOR )
21
.
THERMO CONTROL ( FOR WIRED REMOTE SENSOR )
22
.
HEAT INSULATION CONDITION ( BUILDING INSULATION )
20
Ts + 1°F
(Ts + 0.5°C)
Ts - 1°F
(Ts - 0.5°C)
Ts - 1°F
(Ts - 0.5°C)
Ts + 1°F
Compressor ON
(Ts + 0.5°C)
( Fig. 10 : For cooling operation )
Ts
Ts
Compressor OFF
( Fig. 11 : For heating operation )
Compressor ON
Compressor OFF
Ts + 1°F
(Ts + 0.5°C)
Ts - 1°F
(Ts - 0.5°C)
Compressor ON
Compressor OFF
Compressor ON
Compressor OFF
Ts : Setting temperature
Ts : Setting temperature
( Fig. 12 : For cooling operation )
( Fig. 13 : For heating operation )
This setting can make the room temperature control more suitable for homes or buildings
with high insulation (Function Number 95).
When the thermo sensor is turned ON it controls the compressor frequency at
initial start to prevent overshoot in heating or cooling.
When room temperature is controlled by the Indoor unit sensor, compressor operation
is as shown in Fig. 10 and 11 .
But, adjustment is possible by the room temperature correction function setting.
(Function Number 30 or 31)
When room temperature is controlled by the Wired remote sensor, compressor
operation is as shown in Fig. 12 and 13 .
But, adjustment is possible by the room temperature correction function setting.
(Function Number 92 or 93)
01-14
Содержание R410A
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 23: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 76: ...Jan 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...