background image

1.     ETERNUS AX/HX Installation
      Outlet/Socket Specifications

Site Planning Guide

44

When the power distribution units are separately connected to line 0 (PSU#0) and line 1 (PSU#1), the availabil-
ity of the power supply facilities is improved.

...

ETERNUS

Line 0

Line 1

PSU

PSU

Drive shelf

PSU

PSU

PSU

PSU

Controller shelf

Power distribution unit

Power distribution unit

Drive shelf

P

o

w

er supply

facility

P

o

w

er supply

facility

Содержание ETERNUS AX Series

Страница 1: ...FUJITSU Storage ETERNUS AX series All Flash Arrays ETERNUS HX series Hybrid Arrays P3AG 4822 10ENZ0 Requirements for transportation installation Site Planning Guide ...

Страница 2: ...ge Size 27 Installation Area 28 Installation Environment 30 Air Conditioning 30 Installation Methods 31 Load Bearing Capacity for Floors 32 Outlet Socket Specifications 33 Specifications for Optional Power Supply Products 34 Required Number of Outlets Sockets 38 Circuit Protectors 38 Input Power Supply Lines 43 2 Rack Installation Specifications 45 Rack Installation Requirements 45 Placement in th...

Страница 3: ...ng to Power Sockets 43 Figure 24 Single Line Power Supply When Connecting to Power Sockets 43 Figure 25 Single Line Power Supply When Connecting to a UPS Unit 43 Figure 26 Example Rack Installation ETERNUS AX1100 AX2100 AX2200 ETERNUS HX2100 HX2200 46 Figure 27 Example Rack Installation ETERNUS AX4100 ETERNUS HX6100 47 Figure 28 Mini SAS HD Cables between Shelves for a Single Controller Shelf 48 F...

Страница 4: ... Figure 44 Two Node Configuration Using Cluster Switches Nexus 9336C for 100GBASE Port Connections 61 Figure 45 Four Node Configuration Using Cluster Switches Nexus 3232C for 100GBASE Port Connections 62 Figure 46 Two Node Configuration Using Cluster Switches Nexus 3232C for 100GBASE Port Connections 63 Figure 47 Unit Installation Area 66 ...

Страница 5: ...f Each Power Cord 33 Table 17 Specifications for AC250V Power Cords IEC60320 C13 NEMA L6 15P 34 Table 18 Specifications for AC250V Power Cords IEC60320 C19 C20 34 Table 19 Specifications for AC250V Power Cords IEC60320 C19 NEMA L6 20P 34 Table 20 Specifications for AC100V Power Cords IEC60320 C13 NEMA 5 15P 35 Table 21 Specifications for AC100V AC250V Power Cords IEC60320 C13 C14 35 Table 22 Speci...

Страница 6: ...US AX HX is designed to be connected to Fujitsu servers Fujitsu SPARC Servers PRIMEQUEST PRIM ERGY and other servers or non Fujitsu servers This manual describes the environmental requirements that are necessary to install and use the ETERNUS AX HX This manual is intended for use of the ETERNUS AX HX in regions other than Japan Please carefully review the information outlined in this manual Copyri...

Страница 7: ...el is available at https www fujitsu com global support products computing storage manuals list html Document Conventions Notice Symbols The following notice symbols are used in this manual Start of Production for This Product Production for the ETERNUS AX1100 AX2100 AX4100 and ETERNUS HX2100 HX2200 HX6100 has started from 2020 Production for the ETERNUS AX2200 has started from 2021 Indicates info...

Страница 8: ... other users and their property if the ETER NUS AX HX is not used properly This symbol indicates IMPORTANT information for the user to note when using the ETERNUS AX HX Electric Shock The triangle emphasizes the urgency of the WARNING and CAUTION contents Inside the triangle and above it are details concerning the symbol e g Electrical Shock No Disassembly The barred Do Not circle warns against ce...

Страница 9: ...e 2 Efficiency and the power factor of the power supply unit Table 3 Table 1 Installation Specifications ETERNUS AX1100 AX2100 AX2200 Item ETERNUS AX1100 ETERNUS AX2100 ETERNUS AX2200 Dimensions W D H 2 5 type controller shelf 480 483 85 mm 2U 480 483 85 mm 2U 483 543 87 mm 2U DS224C 2 5 type drive shelf 480 484 85 mm 2U NS224 drive shelf 483 543 87 mm Power distribution unit 2U 1 485 123 44 mm 2 ...

Страница 10: ...4 AC100 120V 1 825 kJ h 8 921 kJ h 6 667 kl h AC200 240V 1 789 kJ h 8 759 kJ h 6 937 kJ h Maximum amount of exhaust air Controller shelf Drive shelf 2 5 type 3 5 type NS224 60 drive type Environmental conditions Tempera ture Operating 5 45 C 5 10 35 C 6 Not operating 40 70 C During shipment 40 70 C Temperature gradient 15 C Hr or less Humidity Operating 5 8 90 RH Not operating 10 95 RH During ship...

Страница 11: ...t of the PSU ETERNUS AX4100 Each installation specification is shown below Installation specifications Table 4 Sound level of the drive shelf Table 5 Efficiency and the power factor of the power supply unit Table 6 Table 4 Installation Specifications ETERNUS AX4100 DS224C NS224 Sound pressure level 51 dBA 49 8 dBA Sound power level 6 9 B 6 4 B Component name 80PLUS Efficiency Power factor Output S...

Страница 12: ...ype AC100 120V 5 688 kJ h AC200 240V 5 501 kJ h Drive shelf DS224C 2 5 type AC100 120V 1 404 kJ h AC200 240V 1 379 kJ h NS224 AC100 120V 3 053 kJ h AC200 240V 2 916 kJ h Maximum configuration 4 AC100 120V 33 768 kJ h AC200 240V 33 077 kJ h Maximum amount of exhaust air Controller shelf Drive shelf 2 5 type 3 5 type 60 drive type Environmental conditions Tempera ture Operating 5 10 35 C Not operati...

Страница 13: ... B Component name 80PLUS Efficiency Power factor Output Shelf 20 1 50 1 100 1 50 1 ETERNUS AX4100 Platinum 93 45 94 18 91 43 1 000 Single output DS224C drive shelf 91 8 94 2 92 7 0 980 NS224 drive shelf 93 45 94 18 91 43 1 000 Item ETERNUS HX2100 ETERNUS HX2200 Dimensions W D H 3 5 type controller shelf 480 508 87 mm 2U 2 5 type controller shelf 480 483 85 mm 2U DS212C 3 5 type drive shelf 480 505...

Страница 14: ... configuration 4 AC100 120V 3 596 W 3 672 VA 3 715 W 3 796 VA AC200 240V 3 901 W 3 954 VA 3 688 W 3 738 VA Maximum heat generation 2 Controller shelf 3 5 type AC100 120V 1 786 kJ h AC200 240V 1 753 kJ h 2 5 type AC100 120V 2 214 kJ h AC200 240V 2 182 kJ h Drive shelf DS212C 3 5 type AC100 120V 1 217 kJ h 1 217 kJ h AC200 240V 1 195 kJ h 1 195 kJ h DS224C 2 5 type AC100 120V 1 534 kJ h 1 426 kJ h A...

Страница 15: ...ure Operating 5 5 45 C Not operating 40 70 C During shipment 40 70 C Temperature gradient 15 C Hr or less Humidity Operating 5 8 90 RH Not operating 10 95 RH During shipment 10 95 RH Humidity gradient 30 day or less Maximum wet bulb temperature 29 C Altitude above sea level 0 3 048 m Airborne dust 0 15 mg m3 or less Gas concentration tolerance level Cl2 6 8 ppb or less H2S 7 1 ppb or less SO2 37 p...

Страница 16: ...6 2 kg DS460C 60 drive type drive shelf 112 kg 116 kg Power distribution unit 2U 1 3 0 kg 2 Power Voltage AC 100 120V AC 200 240V Phase Single Frequency 50 Hz 60 Hz Maximum power consumption 2 Controller shelf AC100 120V 1 512 W 1 543 VA AC200 240V 1 470 W 1 500 VA Drive shelf DS212C 3 5 type AC100 120V 338 W 345 VA AC200 240V 332 W 340 VA DS224C 2 5 type AC100 120V 396 W 405 VA AC200 240V 389 W 3...

Страница 17: ...ronmental conditions Tempera ture Operating 5 10 35 C Not operating 40 70 C During shipment 40 70 C Temperature gradient 15 C Hr or less Humidity Operating 5 8 80 RH Not operating 10 95 RH During shipment 10 95 RH Humidity gradient 30 day or less Maximum wet bulb temperature 29 C Altitude above sea level 0 3 048 m Airborne dust 0 15 mg m3 or less Gas concentration tolerance level Cl2 6 8 ppb or le...

Страница 18: ...ack Expansion rack Dimensions W D H 700 1 050 2 000 mm 700 1 272 2 000 mm including anti tipping stabilizer Maximum weight 129 kg 103 kg Service area Refer to Figure 12 under Installation Area page 28 Number of units 42U Item Specification Base rack Expansion rack Dimensions W D H 800 1 200 2 000 mm 800 1 432 2 000 mm including anti tipping stabilizer Maximum weight 155 kg 125 kg Service area incl...

Страница 19: ...ntroller shelf The dimensions are approximations and do not include protruding parts 2 5 Type Controller Shelf Figure 1 2 5 Type Controller Shelf Dimensions ETERNUS AX1100 AX2100 ETERNUS HX2200 Figure 2 2 5 Type Controller Shelf Dimensions ETERNUS AX2200 447 mm without the flanges 480 mm with the flanges 85 mm 483 mm 447 mm without the flanges 483mm with the flanges 87 mm 543 mm ...

Страница 20: ...Controller Shelf Figure 3 3 5 Type Controller Shelf Dimensions ETERNUS HX2100 4U Controller Shelf Figure 4 4U Controller Shelf Dimensions ETERNUS AX4100 HX6100 447 mm without the flanges 480 mm with the flanges 87 mm 508 mm 447 mm without the flanges 483 mm with the flanges 175 mm 828 mm ...

Страница 21: ...e Shelf Dimensions The diagrams below show the dimensions of a drive shelf The dimensions are approximations and do not include protruding parts DS224C 2 5 Type Drive Shelf Figure 6 DS224C 2 5 Type Drive Shelf Dimensions 447 mm without the flanges 483 mm with the flanges 87 mm 543 mm 447 mm without the flanges 480 mm with the flanges 85 mm 484 mm ...

Страница 22: ... 3 5 Type Drive Shelf Figure 7 DS212C 3 5 Type Drive Shelf Dimensions DS460C 60 Drive Type Drive Shelf Figure 8 DS460C 60 Drive Type Drive Shelf Dimensions 447 mm without the flanges 480 mm with the flanges 87 mm 505 mm 449 mm without the flanges 486 mm with the flanges 176 mm 922 mm ...

Страница 23: ...s of a 19 inch rack and an anti tipping stabilizer The dimensions are approximations and do not include protruding parts For specification information that is required for securing a rack refer to Figure 14 under Installation Methods page 31 Figure 9 19 inch Rack Dimensions Top Front Rear Side Bottom 2 000 mm 1 050 mm 700 mm ...

Страница 24: ...1 ETERNUS AX HX Installation Rack Dimensions Site Planning Guide 24 Figure 10 19 inch Wide Rack Dimensions Top Front Rear Side Bottom 2 000 mm 1 200 mm 800 mm ...

Страница 25: ...1 ETERNUS AX HX Installation Rack Dimensions Site Planning Guide 25 Figure 11 Anti Tipping Stabilizer Dimensions 742 mm 250 mm 80 mm Installation image of the L shaped stabilizer Top Front Side ...

Страница 26: ...agnetic Compatibility EMC EN 55032 Class A EN 55024 2010 EN 61000 3 2 2014 EN 61000 3 3 2013 FCC Part 15 Subpart B Class A ICES 003 Class A VCCI Class A JIS C 61000 3 2 CNS 13438 2006 AS NZS CISPR 32 Class A 2015 TP TC 020 2011 KN32 Class A KN35 Environmental compliance This product complies with the requirements of the European Union directives listed below 2014 35 EU Low Voltage Directive 2014 3...

Страница 27: ...talled When optional drives are ordered without preinstallation each drive is shipped in an individual package or in a box of 6 or 10 drives Component Package size W D H Maximum weight Reinforced cardboard for 19 inch racks 950 1 450 2 190 mm 1 Approximately 240 kg 1 2 Reinforced cardboard for 19 inch wide racks 1 030 1 550 2 170 mm 1 Approximately 260 kg 1 2 Controller shelf 2 5 type 810 490 710 ...

Страница 28: ...lled in a Fujitsu 19 inch rack Secure service areas in the front and rear of the 19 inch rack Figure 12 Installation Area and Service Area When the Lifter Is Not Used 1 The areas on the left and right of the front service area are not required if the ETERNUS AX HX is installed in the rack Rear service area Front service area 850 mm or more 1 016 mm or more 19 inch rack 560 mm or more 1 560 mm or m...

Страница 29: ...for Installing a DS460C Drive Shelf 60 Drive in a Rack A lifter must be used to ensure safety during the installation of the drive shelf in the rack Secure a space required to use the lifter When a drive is added or replaced the front left and right of the rack must be secured as service areas to pull out the drawer The drive shelf weighs a maximum of 115 kg Be sure to maintain the load bearing ca...

Страница 30: ...ation the room size whether other storage systems are installed and how many people are present in the room Take the following points into consideration when installing the air conditioning system Ambient Temperature An ETERNUS AX HX is cooled by taking in air through the front intakes and pushing out the exhaust air through the rear of the ETERNUS AX HX If the intake air temperature does not meet...

Страница 31: ...pling over The installation method that should be used depends on the installation location the floor conditions and the type of racks where the ETERNUS AX HX is to be installed Contact your installation contractor for more details regarding installation and how the installation should actually be performed An installation diagram when installing a rack or the floor dimensions of the rack is shown...

Страница 32: ... is maintained Load bearing capacity of the floor ETERNUS AX HX weight Installation area that includes service areas If the condition above is not satisfied additional measures are required to ensure sufficient load bearing capac ity Contact your installation contractor for details about the necessary measures that must be taken 1 093 6 mm leveling feet 906 8 mm caster Front Rear 623 mm caster 670...

Страница 33: ...ry power is supplied from the other power source 1 The controller shelf of the ETERNUS AX4100 and the controller shelf of the ETERNUS HX6100 have four power supply units Current Consumption The following table shows the current consumption guideline of each power cord that is used for ETERNUS AX HX connections Table 16 Maximum Current Consumption of Each Power Cord Incompatible with AC100V When po...

Страница 34: ...low AC200V Table 17 Specifications for AC250V Power Cords IEC60320 C13 NEMA L6 15P AC200V power cords are used to connect devices to the IEC60320 C19 power socket type These power cords can be used if the specifications of the connection device allow AC200V Table 18 Specifications for AC250V Power Cords IEC60320 C19 C20 AC200V power cords are used to connect devices to the NEMA L6 20R power socket...

Страница 35: ...ications for AC100V AC250V Power Cords IEC60320 C13 C14 Usage Plug type Socket Socket type Power supply unit Power cord length Voltage rating current rating Used for connection between the ETERNUS AX HX and the socket IEC60320 C13 NEMA 5 15P NEMA 5 15P IEC60320 C13 3 0 m 125V 15A Usage Plug type Socket Socket type Power supply unit Power cord length Voltage rating current rating Used for connectio...

Страница 36: ...to all the connected devices using one of the mod ules of the power distribution unit Figure 16 Power Distribution Unit AC24A 200V 2U 16 Outlets Table 22 Specifications for Power Distribution Units AC24A 200 240V 2U 16 Outlets Outlet Inlet Voltage rating current rating Socket type Socket Plug type Socket type Socket Power cord length IEC60320 C13 NEMA L6 30P NEMA L6 30R 4 0m Rating 200 240V 24A Si...

Страница 37: ... 2U Six Outlets Table 23 Specifications for Power Distribution Units AC24A 200 240V 2U Six Outlets Table 24 Specifications for Power Distribution Units AC24A 200 240V 2U Six Outlets for Korea Outlet Inlet Voltage rating current rating Socket type Socket Plug type Socket type Socket Power cord length IEC60320 C19 NEMA L6 30P NEMA L6 30R 4 4m Rating 200 240V 24A Outlet Inlet Voltage rating current r...

Страница 38: ...ive shelf With Power Distribution Units Two power sockets are required for each power distribution unit Circuit Protectors Protection coordination must be secured between the distribution board circuit protectors and the ETERNUS AX HX or power distribution units to protect the ETERNUS AX HX by blocking the failed circuit immediately when a power supply input error occurs Distribution board circuit...

Страница 39: ...e distribution board s circuit protectors have a breaking characteristic that is faster than D the breaker may trip when a power supply unit in the storage system fails When the breaker trips a shutoff occurs on multiple power supply units connected to the same connection line as the failed power supply unit 1 Relationship between the size of excess current and operation time 0 01 0 02 0 04 0 06 0...

Страница 40: ...a Power Supply Connection When a Power Distribution Unit Six Outlets Is Used PSU Power Supply Units CP Circuit Protectors Do not connect just one power distribution unit to multiple ETERNUS storage systems In addition do not con nect just one circuit protector of a power distribution unit to multiple ETERNUS storage systems When power cords are connected to a single power supply line the connectio...

Страница 41: ...consumption of each CP four outlets OUT1 to OUT4 or OUT5 to OUT8 12A or less Current consumption of each inlet cable 24A or less Figure 20 Example of a Power Supply Connection When a Power Distribution Unit 16 Outlets Is Used PSU Power Supply Units CP Circuit Protectors CP CP CP CP CP CP PSU PSU PSU PSU Controller shelf Drive shelf ETERNUS PSU PSU Drive shelf PSU PSU Drive shelf To power supply fa...

Страница 42: ... used Figure 22 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used PSU Power Supply Units CP Circuit Protectors CAUTION Do Only connect the ETERNUS AX HX to circuit protectors Distribution board Line 0 To power supply facility To power supply facility Line 1 CP CP CP CP Power distribution unit CP CP PSU PSU Drive shelf ETERNUS AX4100 or ETERNUS HX6100 PSU PSU PSU PSU C...

Страница 43: ... However a single power supply facility configuration is also allowed for the entire system optimization including the server When selecting a single configuration take into consideration the availability of the system Figure 23 Dual Line Power Supply When Connecting to Power Sockets Figure 24 Single Line Power Supply When Connecting to Power Sockets Figure 25 Single Line Power Supply When Connect...

Страница 44: ...ion units are separately connected to line 0 PSU 0 and line 1 PSU 1 the availabil ity of the power supply facilities is improved ETERNUS Line 0 Line 1 PSU PSU Drive shelf PSU PSU PSU PSU Controller shelf Power distribution unit Power distribution unit Drive shelf Power supply facility Power supply facility ...

Страница 45: ...ow the 2U shelves The center of gravity must be taken into consideration to prevent a rack from toppling over Shelves should generally be installed from bottom to top to lower the center of gravity and to ensure the safe use of racks Shelves are installed in the following order from bottom to top Table 26 Shelf Installation Order 1 Uninterruptible Power Supply When an AX4100 or HX6100 is ordered t...

Страница 46: ...is the same type as the one included in the controller shelf 3 DS460C 4 DS224C 5 DS212C Rack Wide rack Drive shelf Controller shelf Controller shelf PDU 41U 40U 39U 38U 37U 36U 35U 34U 33U 32U 31U 30U 29U 28U 27U 26U 25U 24U 23U 22U 21U 20U 19U 18U 17U 16U 15U 14U 13U 12U 11U 10U 42U 9U 8U 7U 6U 5U 4U 3U 2U 1U 41U 40U 39U 38U 37U 36U 35U 34U 33U 32U 31U 30U 29U 28U 27U 26U 25U 24U 23U 22U 21U 20U ...

Страница 47: ...s case secure a space of 1U or more at the bottom when installing the ETERNUS AX HX If drive shelves are to be added in the future securing sufficient space for power distribution units in the bot tom of the rack is recommended If devices are installed above and below the ETERNUS AX HX and there is a difference in depth of 100 mm or more leave a space of 1U above the ETERNUS AX HX so the rear of t...

Страница 48: ...shelf to the next power distribution unit if the total current capacity of the current consumption value of the power cords that connect from outlets OUT5 to OUT8 exceeds 12A Power Distribution Units 2U 6 Outlets 24A For each power distribution unit the total current capacity of the current consumption value of the power cords that connect from outlets OUT1 to OUT3 must be 24A or less Shelves Inte...

Страница 49: ...ications Rack Installation Requirements Site Planning Guide 49 Figure 29 Mini SAS HD Cables between Shelves When Connecting a 4U Drive Shelf 1m cable Controller shelf Drive shelf 1 Drive shelf 2 Drive shelf 3 0 5m cable 2m cable ...

Страница 50: ...on location of the racks and the connection destination If the controller shelf and a drive shelf are installed in the same rack Use four 2 m cables If the controller shelf and a drive shelf are installed in adjacent racks Use four 5 m cables If drive shelves are installed one on top of the other in the same rack Use four 0 5 m cables If drive shelves are installed approximately 10U away from each...

Страница 51: ...elf The number and length of the mini SAS HD cables that are used varies depending on the installation location of the racks and the connection destination If the controller shelf and a drive shelf are installed in the same rack Use four 2 m cables If the controller shelf and a drive shelf are installed in adjacent racks Use four 5 m cables If drive shelves are installed one on top of the other in...

Страница 52: ... Rack Installation Requirements Site Planning Guide 52 Figure 32 Mini SAS HD Cables between Shelves When Connecting between the ETERNUS HX6100 and Two DS212C Drive Shelves Controller shelf Drive shelf 2 Drive shelf 1 0 5m cable 2m cable ...

Страница 53: ...tion Requirements Site Planning Guide 53 Figure 33 Mini SAS HD Cables between Shelves When Adding Two DS212C Drive Shelves to the Configuration in Figure 32 Drive shelf 4 Drive shelf 3 Controller shelf Drive shelf 2 Drive shelf 1 0 5m cable 2m cable ...

Страница 54: ...US AX4100 and One NS224 Drive Shelf Figure 35 Mini SAS HD Cables between Shelves When Adding NS224 and DS224C Drive Shelves to the Configuration in Figure 34 Controller shelf NS224 drive shelf 2m cable Drive shelf Controller shelf NS224 drive shelf 1 NS224 drive shelf 2 2m cable provided with the controller shelf 2m NS224 cable to be added 2m DS224C cable to be added ...

Страница 55: ... Attach Cable Connection Cables Used Between Nodes and Switches For the ETERNUS AX HX series a cluster comprises multiple HA pairs For a cluster configured with two or more HA pairs four or more nodes the cluster network connection must be used Cluster switches are used for the cluster network connection Cluster switches are also used for the MetroCluster configuration Two cluster switches are use...

Страница 56: ... used for each HA pair two nodes A total of eight cable connections four nodes connections is possible Figure 38 Two Node Configurations Using Cluster Switches Nexus 3132 VXLAN for 10GBASE Port Connections 1 SFP ports 4 on a switch cannot be used at the same time as QSFP port 1 Enable the SFP port when connecting cables to the SFP ports on the switch Figure 39 Two Node Configurations Using Cluster...

Страница 57: ...ur 10GBASE ports breakout connections Two cables are required for every two HA pairs four nodes Two cables are also required for a single HA pair two nodes In this case half the terminals of the breakout cables are left unconnected Figure 40 Four Node Configuration Using Cluster Switches Nexus 9336C for 40GBASE Port Connections Cables used between nodes and switches Node Node Node Node ...

Страница 58: ...g Guide 58 Figure 41 Two HA Pair Four Node Configuration Using Cluster Switches Nexus 3132 VXLAN for 40GBASE Port Connections 1 If SFP ports are enabled QSFP port 1 cannot be used Use port 2 to 6 SFP port 1 QSFP port 1 1 Node Node Node Node Cables used between nodes and switches ...

Страница 59: ...fications Rack Installation Requirements Site Planning Guide 59 Figure 42 Two HA Pair Four Node Configuration Using Cluster Switches Nexus 3232C for 40GBASE Port Connections Cables between nodes and switches Node Node Node Node ...

Страница 60: ...SE port into four 25GBASE ports breakout connections Two cables are required for every two HA pairs four nodes Two cables are also required for a single HA pair two nodes In this case half the terminals of the breakout cables are left unconnected Figure 43 Two Node Configuration Using Cluster Switches Nexus 9336C for 100GBASE Port Connections Cables between nodes and switches Node Node Node Node ...

Страница 61: ...onnection When connecting to a 100GBASE port four cables are required for every HA pair two nodes A total of 48 cable connections 12 nodes connections is possible Figure 44 Two Node Configuration Using Cluster Switches Nexus 9336C for 100GBASE Port Connections Cables between nodes and switches Direct attach cables HA connection Node Node ...

Страница 62: ...ode Configuration Using Cluster Switches Nexus 3232C for 100GBASE Port Connections 1 QSFP ports 4 to 6 are configured as breakout connections 25GBASE 4 by the configuration in the Nexus_3232C_RCF_v1 6 Cluster HA Breakout txt file Cables between nodes and switches Node Node QSFP port 1 1 Node Node SFP ports ...

Страница 63: ...Rack Installation Requirements Site Planning Guide 63 Figure 46 Two Node Configuration Using Cluster Switches Nexus 3232C for 100GBASE Port Connections Cables between nodes and switches Node Node HX6100 Direct attach cables HA connection ...

Страница 64: ...ed in 19 inch wide racks Precautions for Installing a DS460C Drive Shelf in a Rack Because the depth is larger than other shelves install the shelf in a 19 inch rack designated by Fujitsu or a rack with a rack space of 922 mm external depth of the drive shelf plus an additional 100 mm or more cable area Refer to Non Fujitsu Racks page 65 for the specification of the rack space in a rack Model Rack...

Страница 65: ...ting holes for rack mount kits ordered before September 30 2021 Square hole 9 5 0 1 mm recommended Round hole 7 1 0 1 mm recommended Size for mounting holes for rack mount kits ordered after October 1 2021 Table 30 Size for Mounting Holes for Rack Mount Kits Ordered after October 1 2021 1 Note that the size of the mounting holes on the drive shelves included in the basic configuration differs from...

Страница 66: ...allation according to the requirements described in Installation Specifications page 9 and Installation Environment page 30 Specification Condition 1 Rack front space Space between the fixed part of the ETERNUS AX HX on the front side and the front of the rack 50 mm or more 2 Mount bracket length Size between each end of the front and rear rack pillars 600 mm to 790 mm 3 Rack space Space between t...

Страница 67: ... was prepared with the utmost attention to detail However Fujitsu shall assume no responsibility for any operational problems as the result of errors omissions or the use of information in this manual Fujitsu assumes no liability for damages to third party copyrights or other rights arising from the use of any information in this manual The content of this manual may not be reproduced or distribut...

Страница 68: ......

Отзывы: