1. ETERNUS AX/HX Installation
Outlet/Socket Specifications
Site Planning Guide
38
Required Number of Outlets/Sockets
The number of power outlets/sockets required to install the ETERNUS AX/HX depends on the number of shelves
and power distribution units.
It is recommended that the power cords of the shelves are connected to the power distribution units that are
installed in the same rack. Secure the necessary number of power outlets within the same rack to avoid connect-
ing power cords to power outlets in different racks. It may be necessary to purchase additional power distribution
units depending on the installation locations of shelves.
■
Without Power Distribution Units
Two power sockets are required for each controller shelf and drive shelf.
■
With Power Distribution Units
Two power sockets are required for each power distribution unit.
Circuit Protectors
Protection coordination must be secured between the distribution board circuit protectors and the ETERNUS AX/
HX or power distribution units to protect the ETERNUS AX/HX by blocking the failed circuit immediately when a
power supply input error occurs.
Distribution board circuit protectors must satisfy the following required conditions and breaking characteristics.
■
Required Conditions
The distribution board circuit protectors must satisfy the required conditions that are listed below.
Table 25 Required Conditions for Distribution Board Circuit Protectors
Connected device
Power supply voltage
Current capacity
Power distribution unit (AC24A/200V, 2U, 16 outlets)
AC 200 – 240V
24A
Power distribution unit (AC24A/200V, 2U, six outlets)
AC 200 – 240V
24A
ETERNUS AX/HX (without power distribution units)
AC 100 – 120V
AC 200 – 240V
15A
Содержание ETERNUS AX Series