Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AS*B24LDC
[Condition]
Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*B24LDC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*B24LDC
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
unit overall current with the current clamp meter at Power Cable.
08-02
0.70
0.80
0.90
1.00
1.10
1.20
1.15
15
20
25
30
35
In/Outdoor ambient temperature[ C]
Lo
w
-p
re
ss
ur
e
of
o
ut
do
or
u
ni
t[M
P
a]
RH70%
RH60%
RH50%
8.0
8.5
9.0
9.5
10.0
10.5
11.0
15
20
25
30
35
In/Outdoor ambient temperature[ C]
to
ta
l e
le
ct
ric
c
ur
re
nt
[A
]
0.75
0.85
0.95
1.05
[50Hz-230V]
RH70%
RH60%
RH50%
[50Hz-230V]
Содержание B24LDC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Страница 66: ......
Страница 67: ......
Страница 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Страница 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Страница 70: ......
Страница 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...