18. DEFROST OPERATION CONTROL
(1). CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects
the temperature lower than the values shown in Table 15.
(Table 15 : Condition of starting Defrost Operation)
AS*B24LDC
AS*B24LDC
AS*B24LDC
1 time defrosting
after starting
operation
ST
Defrosting after 2
time upon starting
operation
ND
Compressor operating time
Less than 17 minutes 17 to 60 minutes 60 minutes to 4 hours
After 4 hours
Does not operate
- 9 C
- 5 C
- 3 C
Less than 35 minutes
35 minutes to
4 hours
Does not operate
Compressor operating time
After 4 hours
- 3 C
- 6 C
(2). CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when the conditions become as shown in Table 16.
(Table 16 : Defrost Release Condition)
Release Condition
Outdoor heat exchanger temperature sensor value is higher than 13 C or
Compressor operation time has passed 15 minutes.
05-15
Содержание B24LDC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Страница 66: ......
Страница 67: ......
Страница 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Страница 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Страница 70: ......
Страница 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...