(5).HEATING OPERATION
Switch the airflow [AUTO], and the
(Fig.7)
indoor fan motor will run according
airflow change - over ( Heating:AUTO)
to a room temperature, as shown in
When the room
Figure 7.
temperature rises
On the other hand, if switched L O W m o d e
[HIGH]
[QUIET], the indoor motor
will run at a constant airflow of [HEAT]
operation modes QUIET, LOW, MED, MED mode
HIGH, as shown in Table 5.
MED +mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(6).COOL AIR PREVENTION CONTROL (Heating mode)
Indoor heat exchanger Indoor heat exchanger
temperature temperature
Cool air prevention
S-Lo
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
05-06
-1.0 C
-2.0 C
-1.5 C
-2.5 C
47 C
40 C
37 C
30 C
40 C
Hi
Me+
Lo
34 C
32 C
28 C
Содержание B24LDC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Страница 66: ......
Страница 67: ......
Страница 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Страница 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Страница 70: ......
Страница 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...