0.5
sec.
2 times
0.5 sec
2 times
Room temperature
thermistor defective
The room temperature thermistor detected a abnormal temperature when the power was turned on.
> Remote control does not operate.
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.5 sec
3 times
Indoor Heat Exchanger
Thermistor Error
The detection value of the indoor heat exchanger thermistor is either open or shorted when the power is ON.
> Remote control does not operate.
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.5
sec.
3 times
0.5 sec
2 times
Discharge Thermistor
Error
The detection value of the discharge thermistor is either open or shorted
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.5 sec
3 times
Outdoor Heat Exchanger
Thermistor Error
The detection value of the outdoor heat exchanger thermistor is open.
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective
0.5 sec
4 times
Outdoor Temperature
Thermistor Error
The detection value of the outdoor temperature thermistor is either open or shorted
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective.
0.5 sec
8 times
The detection value of the compressor thermistor is either open or shorted
> Compressor, Outdoor Fan : OFF (It automatically releases when the normal value is detected.)
[Diagnosis Point]
07
-0
4
Indoor unit
thermistor error
Outdoor unit
thermistor error
Compressor Temperature
Thermistor Error
- Check Thermistor resistance value (Refer to “Thermistor characteristics table”).
- Controller PCB defective
02
04
0C
06
0A
15
Содержание B24LDC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Страница 66: ......
Страница 67: ......
Страница 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Страница 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Страница 70: ......
Страница 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...