0.5
sec.
4 times
0.5 sec
3 times
Main Relay Error
No Display
No Display
After 2 minutes 20 seconds of stopping operation, the signal from outdoor unit is received even though the main
relay is OFF.
> Main Relay OFF continues (Outdoor Unit OFF Command)
[Diagnosis Point]
- Main Relay defective
- Controller PCB defective.
0.5 sec
4 times
The power supply frequency can not be recognized after 4 seconds of power ON.
> Permanent stop.
[Diagnosis Point]
- Controller PCB defective.
0.5 sec
7 times
VDD permanence stop
protection
(Electric air clean)
0.5 sec
8 times
Reverde-VDD
permanence stop
protection
(Electric air clean power
supply circuit abnormal)
07
-0
5
Indoor unit
Controller
Error
0.5 sec
2 times
Forced Auto Switch
Error
Forced Auto Switch becomes ON for 10 consecutive seconds.
> It indicates the error but the operation continues.
[Diagnosis Point]
- Check if forced Auto Switch is kept pressed.
- Forced Auto Switch defective.
- Controller PCB defective.
Power Supply Frequency
Detection Error
20
22
21
When the air cleanness monitor trial protection operates 4 times.
> Only clean air permanent stop.
[Diagnosis Point]
- The front panel is closed.
- The foreign body such as dust doesn't adhere.
The air clean operation signal was detected for 1 minute at time of air clean mode OFF.
> All stop. Not operate remote controller.
[Diagnosis Point]
- Electric air clean defective.
- Controller PCB defective.
Содержание B24LDC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 7: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 13: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 34: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 64: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 65: ...REPLACEMENT PARTS Models AS B24LDC INDOOR UNIT 09 01 ...
Страница 66: ......
Страница 67: ......
Страница 68: ...REPLACEMENT PARTS 09 04 Models AS B24LDC ...
Страница 69: ...REPLACEMENT PARTS 09 05 Model AO S24LDC ...
Страница 70: ......
Страница 88: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 91: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS20032006 FEB 2006 Printed in Japan ...