4) Room temperature sensor control for cooling
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
5) Room temperature sensor control for heating
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
6) Auto restart
Enables or disables automatic restart after a power interruption.
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external
device.
7) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
Remote controller sensor must be turned on by using the remote controller.
8) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
Setting description
Factory setting
30
00
Standard
♦
01
Slightly lower control
02
Lower control
03
Higher control
Function number
Setting value
Setting description
Factory setting
31
00
Standard
♦
01
Lower control
02
Slightly higher control
03
Higher control
Function number
Setting value
Setting description
Factory setting
40
00
Enable
♦
01
Disable
Function number
Setting value
Setting description
Factory setting
42
00
Indoor unit
♦
01
Both
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
Содержание AUTG09LVLB
Страница 5: ...Part 1 INDOOR UNIT CASSETTE TYPE AUTG09LVLB AUTG12LVLB ...
Страница 16: ... 12 CASSETTE TYPE AUTG09 12LVLB 5 Wiring diagram 5 1 Models AUTG09LVLB and AUTG12LVLB ...
Страница 26: ... 22 CASSETTE TYPE AUTG09 12LVLB 8 2 Sound level check point Microphone Microphone Center 1 5 m Center ...
Страница 42: ... 38 CASSETTE TYPE AUTG09 12LVLB ...
Страница 43: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOTG09LBCB AOTG12LBCB ...
Страница 45: ... 41 OUTDOOR UNIT AOTG09 12LBCB 2 Dimensions 2 1 Models AOTG09LBCB and AOTG12LBCB Unit mm ...
Страница 50: ... 46 OUTDOOR UNIT AOTG09 12LBCB 4 Wiring diagrams 4 1 Models AOTG09LBCB and AOTG12LBCB ...