![Fujitsu AUTG09LVLB Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/fujitsu/autg09lvlb/autg09lvlb_design-and-technical-manual_2343762032.webp)
- 28 -
CASSETTE TYPE
A
U
T
G
09-
12
LV
LB
11. Function settings
To adjust the functions of this product according to the installation environment, various types of
function settings are available.
NOTE:
Incorrect settings can cause a product malfunction.
11-1. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting proce-
dure and the content of each function setting, select appropriate functions for your installation envi-
ronment.
NOTE:
Incorrect settings can cause a product malfunction.
Setting procedure by using wireless remote controller
The function number and the associated setting value are displayed on the LCD of the remote
controller. Follow the instructions written in the local setup procedure supplied with the remote
controller, and select appropriate setting according to the installation environment.
Before turning on the power of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
Then, turn on the power of indoor unit.
Entering function setting mode:
While pressing the FAN button and SET TEMP. ( ) button simultaneously, press the RESET but-
ton to enter the function setting mode.
STEP 1: Setting the remote controller custom code
Use the following steps to select the custom code of the remote controller. (Note that the air condi-
tioner cannot receive a custom code if the air conditioner has not been set for the custom code.)
The custom codes that are set through this process are applicable only to the signal in the function
setting.
For details on how to set the custom codes through the normal process, refer to
ting for wireless remote controller”
NOTES:
• The air conditioner custom code is set to “A” prior to shipment.
• The remote controller resets to custom code “A” when the batteries on the remote controller are
replaced. If you use a custom code other than code “A”, reset the custom code after replacing the
batteries.
• If you do not know the air conditioner custom code setting, try each of the custom codes (
→
→
→
) until you find the code that operates the air conditioner.
1. Press the SET TEMP. ( ) ( ) buttons to change the custom code
between
→
→
→
. Match the code on the display to the air condi-
tioner custom code. (Initially set to .) If the custom code does not need
to be selected, press the MODE button, and proceed to
STEP 2
.
2. Press the TIMER MODE button and check that the indoor unit can
receive signals at the displayed custom code.
3. Press the MODE button to accept the custom code, and proceed to
STEP 2
.
4. After completing the function setting, be sure to turn off the power and
turn it on again.
Содержание AUTG09LVLB
Страница 5: ...Part 1 INDOOR UNIT CASSETTE TYPE AUTG09LVLB AUTG12LVLB ...
Страница 16: ... 12 CASSETTE TYPE AUTG09 12LVLB 5 Wiring diagram 5 1 Models AUTG09LVLB and AUTG12LVLB ...
Страница 26: ... 22 CASSETTE TYPE AUTG09 12LVLB 8 2 Sound level check point Microphone Microphone Center 1 5 m Center ...
Страница 42: ... 38 CASSETTE TYPE AUTG09 12LVLB ...
Страница 43: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOTG09LBCB AOTG12LBCB ...
Страница 45: ... 41 OUTDOOR UNIT AOTG09 12LBCB 2 Dimensions 2 1 Models AOTG09LBCB and AOTG12LBCB Unit mm ...
Страница 50: ... 46 OUTDOOR UNIT AOTG09 12LBCB 4 Wiring diagrams 4 1 Models AOTG09LBCB and AOTG12LBCB ...