- 30 -
CASSETTE TYPE
A
U
T
G
09-
12
LV
LB
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE:
Setting will not be changed if invalid numbers or setting values are selected.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
For the specific height for each setting value, refer to Chapter 4-1.
However, 09L model can not be installed in high places.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function no.
Functions
1)
11
Filter sign
2)
20
Ceiling height
3)
22
Outlet directions
4)
30
Room temperature sensor control for cooling
5)
31
Room temperature sensor control for heating
6)
40
Auto restart
7)
42
Room temperature sensor switching
8)
44
Remote controller custom code
9)
46
External input control
10)
48
Room temperature sensor switching (Aux.)
Function number
Setting value
Setting description
Factory setting
11
00
Standard (2,500 hours)
01
Long interval (4,400 hours)
02
Short interval (1,250 hours)
03
No indication
♦
Function number
Setting value
Setting description
Factory setting
20
00
Standard
♦
01
High ceiling
Function number
Setting value
Setting description
Factory setting
22
00
4-way
♦
01
3-way
Содержание AUTG09LVLB
Страница 5: ...Part 1 INDOOR UNIT CASSETTE TYPE AUTG09LVLB AUTG12LVLB ...
Страница 16: ... 12 CASSETTE TYPE AUTG09 12LVLB 5 Wiring diagram 5 1 Models AUTG09LVLB and AUTG12LVLB ...
Страница 26: ... 22 CASSETTE TYPE AUTG09 12LVLB 8 2 Sound level check point Microphone Microphone Center 1 5 m Center ...
Страница 42: ... 38 CASSETTE TYPE AUTG09 12LVLB ...
Страница 43: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOTG09LBCB AOTG12LBCB ...
Страница 45: ... 41 OUTDOOR UNIT AOTG09 12LBCB 2 Dimensions 2 1 Models AOTG09LBCB and AOTG12LBCB Unit mm ...
Страница 50: ... 46 OUTDOOR UNIT AOTG09 12LBCB 4 Wiring diagrams 4 1 Models AOTG09LBCB and AOTG12LBCB ...