(The above resistance value is a typical value. There is some distribution. A
Trouble Shooting of Refrigerant Cycle
[Diagnosis Table for Defective Component]
: Item of most possible cause
IPM Protection
Compressor
Location error
Discharge
Temperature Error
Cooling High
Pressure
Protection
Refrigerant leak
Compressor failure(*)
EEV failure (*)
Thermistor failure (*)
(*) Trouble Shooting Method
(1) Checking method of the compressor failure
Insert the AC plug and start up the cooling operation. Input Test operation signal and check if the
compressor operates.
If it does not operate, measure the resistance value of compressor windings between U-V, V-W,
W-U.
If any of the resistance value between U-V, V-W, W-U is not same as others, the compressor is
defective.
Compressor Failure
NORMAL
ASYA07/09/12 LCC
Compressor Case Temperature at 20°C: 0.710 ohm
ASYB09/12LDC
Compressor Case Temperature at 20°C: 0.710 ohm
ASYA14/18LCC
Compressor Case Temperature at 20°C: 0.730 ohm
s it also changes by the
compressor temperature, the measured value may be much different from the above table when
measured right after stopping operation.)
(2) Checking method of EEV failure
- Insert the AC plug and start up the operation. Check if the EEV operates just before compressor is turned
on. (Touch EEV by hand and check it.)
If it does not operate, check if the coil or connector of EEV is removed or loose.
If it operates, check the discharge thermistor / outdoor heat exchanger thermistor / indoor heat
exchanger thermistor.
(Refer to (3) for checking method.)
(3) Checking method of Thermistor
- Check each thermistor if it is removed or the connector is loose.
If there is no problem, remove the connector of the thermistor from the PCB and check the resistance
value (refer to the thermitor characteristics table).
07-09
Содержание AOYR07LCC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S Models ASYA12LCC AOYR12LCC 02 02 unit mm 275 540 2 000 215 790 790 56 290 353 17 ...
Страница 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Страница 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Страница 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Страница 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Страница 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Страница 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Страница 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Страница 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Страница 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Страница 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Страница 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Страница 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Страница 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Страница 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Страница 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Страница 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Страница 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Страница 98: ...Model AOYR07 09LCC 09 19 ...
Страница 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...