(3). ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
A-D
E,F
(Table 19 : Anti-freezing Protection Operation / Release Temperature)
Temperature
Temperature
4°C
4°C
7°C
13°C
(4). COOLING PRESSURE OVERRISE PROTECTION
(Table 20 : Cooling Pressure Over Rise Protection Function Temperature)
When the outdoor unit heat exchange sensor temperature rises to temperature
or greater, the
compressor is stopped and trouble display is performed.
ASYA07/09/12/14/18LCC
67°C
ASYB09/12LDC
67°C
Temperature
(5). HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
05-18
[ ASYA07/12LCC, ASYB09/12LDC ]
[ ASYA14/18LCC ]
46Hz or greater
45Hz
39Hz or greater
38Hz
39
45Hz
38Hz
26
38Hz
25Hz
19
29Hz
18Hz
18
25Hz
OFF
OFF
Indoor heat exchange
temperature
[ Control System ]
Temperature
Temperature
Refer to below
Temperature
Temperature
The compressor frequency is
precisely controlled so that
it does not exceeds Temperature .
It returns to the normal operation
Compressor Operation
18Hz
30
Frequency down every 120 sec
Frequency down every 120 sec
ASYA07/09/12/14/18LCC 55°C
ASYB09/12LDC
55°C
Temp
Temp
Temp
Temp
53°C
53°C
52°C
52°C
50°C
50°C
Содержание AOYR07LCC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S Models ASYA12LCC AOYR12LCC 02 02 unit mm 275 540 2 000 215 790 790 56 290 353 17 ...
Страница 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Страница 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Страница 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Страница 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Страница 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Страница 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Страница 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Страница 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Страница 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Страница 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Страница 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Страница 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Страница 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Страница 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Страница 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Страница 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Страница 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Страница 98: ...Model AOYR07 09LCC 09 19 ...
Страница 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...