Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : ASYA07/09/12LCC
[Condition]
Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m (Height difference 1m)
Power
voltage
50Hz - 230V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*9LSACW series
ASYA12LCC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*9LSACW series
ASYA12LCC
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
0.8
0.9
1
1.1
1.2
1.3
1.4
15
20
25
30
35
In/outdoor ambient temparature (degC)
Low-pressure
o
f
outdoor
unit
MPaG
RH 50%
RH 60%
RH 70%
2.00
2.20
2.40
2.60
2.80
15
20
25
30
35
In/outdoor ambient temparature (degC)
Outdoor
total
electric
c
urrent
A
RH 50%
RH 60%
RH 70%
unit overall current with the current clamp meter at Power Cable.
08-02
0.7
0.8
0.9
1
1.1
1.2
16
18
20
22
24
26
28
30
32
In/outdoor ambient temparature [degc]
Low-pressure
o
f
o
utdoor
unit
[MPa]
RH50%
RH60%
RH70%
3
3.5
4
4.5
16
18
20
22
24
26
28
30
32
In/outdoor ambient temparature [degc]
Outdoor
total
e
lectric
c
urrent
[A]
RH50%
RH60%
RH70%
Содержание AOYR07LCC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S Models ASYA12LCC AOYR12LCC 02 02 unit mm 275 540 2 000 215 790 790 56 290 353 17 ...
Страница 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Страница 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Страница 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Страница 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Страница 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Страница 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Страница 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Страница 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Страница 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Страница 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Страница 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Страница 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Страница 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Страница 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Страница 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Страница 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Страница 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Страница 98: ...Model AOYR07 09LCC 09 19 ...
Страница 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...