10. ELECTRONIC EXPANSION VALVE CONTROL
The most proper opening of the electronic expansion valve is calculated and controlled under the
present operating condition based on the following values.
The compressor frequency, the temperatures detected by the discharge temperature sensor, the
indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature
sensor.
The pulse range of the electronic expansion valve control is between 60 to 480 pulses.
The expansion valve is set at 480 pulses after 110 seconds of stopping compressor.
At the time of supplying the power to the outdoor unit, the initialization of the electronic
expansion valve is operated (528 pulses are input to the closing direction).
11. TEST OPERATION CONTROL
Under the condition where the air conditioner runs, press the test operation button of the remote
control, and the test operation control mode will appear. During test running, the operation lamp
and timer lamp of the air conditioner body twinkle simultaneously. Set the test operation mode,
and the compressor will continue to run regardless of whether the room temperature sensor detects.
The compressor won't enter operation status for 2 minutes and 20 seconds after the compressor is
stopped, even if any operation is given.
At the time when the air conditioner is switched from the cooling mode to heating mode, the
compressor is stopped, and the four-way valve is switched in 2 minutes and 20 seconds later after
the compressor stopped.
When the power was interrupted by a power failure, etc. during operation, the operation contents
at that time are memorized and when power is recovered, operation is automatically started with
the memorized operation contents.
When the power is interrupted and recovered during timer operation, since the timer operation time
is shifted by the time the power was interrupted, an alarm is given by blinking (7 sec ON/2 sec OFF)
the indoor unit body timer lamp.
[Operation contents memorized when the power is interrupted]
Operation mode
Set temperature
Set air flow
Timer mode and timer time
Set air flow Direction
Swing
The test operation mode is released if 60 minutes have passed after setting up the test operation.
12. PREVENT TO RESTART FOR 3 MINUTES ( 3 MINUTES ST )
13. FOUR-WAY VALVE EXTENSION SELECT
14. AUTO RESTART
05-12
Air clean(Only 9/12LDC model)
Содержание AOYR07LCC
Страница 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...D I M E N S I O N S Models ASYA12LCC AOYR12LCC 02 02 unit mm 275 540 2 000 215 790 790 56 290 353 17 ...
Страница 13: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 17: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 22: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 41: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Страница 79: ...9 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 80: ...REPLACEMENT PARTS 09 01 Models ASYA07LCC ASYA09LCC INVERTER ...
Страница 81: ...REPLACEMENT PARTS 09 02 Models ASYA07LCC ASYA09LCC ...
Страница 82: ...REPLACEMENT PARTS 09 03 Models AOYR07LCC AOYR09LCC ...
Страница 83: ...REPLACEMENT PARTS 09 04 Models AOYR07LCC AOYR09LCC ...
Страница 84: ...REPLACEMENT PARTS 09 05 Models AOYR07LCC AOYR09LCC ...
Страница 85: ...REPLACEMENT PARTS 09 06 Models ASYA12LCC INVERTER ...
Страница 86: ...REPLACEMENT PARTS 09 07 Models ASYA12LCC ...
Страница 87: ...REPLACEMENT PARTS 09 08 Models AOYR12LCC ...
Страница 88: ...REPLACEMENT PARTS 09 09 Models ASYA14LCC ASYA18LCC INVERTER ...
Страница 89: ...REPLACEMENT PARTS 09 10 Models ASYA14LCC ASYA18LCC ...
Страница 90: ...REPLACEMENT PARTS 09 11 Models AOYR14LCC AOYR18LCC ...
Страница 91: ...REPLACEMENT PARTS 09 12 Models AOYR14LCC AOYR18LCC ...
Страница 92: ...REPLACEMENT PARTS 09 13 Models ASYB09LDC ASYB12LDC INVERTER ...
Страница 93: ...REPLACEMENT PARTS 09 14 Models ASYB09LDC ASYB12LDC ...
Страница 94: ...REPLACEMENT PARTS 09 15 Models AOYS09LDC AOYS12LDC ...
Страница 96: ...Process Model AOYR07 09LCC Connection of leads to inverter assy REPLACEMENT PARTS 09 17 ...
Страница 97: ...Process Model AOYR07 09LCC Shaping of leads to inverter assy REPLACEMENT PARTS 09 18 ...
Страница 98: ...Model AOYR07 09LCC 09 19 ...
Страница 103: ...10 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Страница 108: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS09022006 FEB 2006 Printed in Japan ...