- 62 -
DUC
T TYPE
ARYG18-5
4LHT
B
P
NOTE:
Range of static pressure is different by model.
If the static pressure is set above maximum range, the setting will be the same as the maximum.
Example:
For 45, 54 type models, setting "170 Pa" (17) to "200 Pa" (20) will be the same as "160 Pa" (16).
For details, refer to Chapter 7. "Fan performance curve" on page 25.
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Type name
Setting of static pressure range
18 type, 24 type, 30 type, and 36 type
30 to 200 Pa
45 type or 54 type
30 to 160 Pa
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
Содержание AOYG18LBCA
Страница 7: ...Part 1 INDOOR UNIT DUCT TYPE ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP ...
Страница 24: ... 18 DUCT TYPE ARYG18 54LHTBP 5 Wiring diagrams 5 1 Models ARYG18LHTBP and ARYG24LHTBP ...
Страница 25: ... 19 DUCT TYPE ARYG18 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 77: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18LBCA AOYG24LBCA AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA ...
Страница 96: ... 90 OUTDOOR UNIT AOYG18 54LB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Страница 97: ... 91 OUTDOOR UNIT AOYG18 54LB 4 2 Model AOYG30LBTA ...
Страница 98: ... 92 OUTDOOR UNIT AOYG18 54LB 4 3 Model AOYG36LBTA ...
Страница 99: ... 93 OUTDOOR UNIT AOYG18 54LB 4 4 Models AOYG45LBTA and AOYG54LBTA ...