![Fujitsu AOYG18LBCA Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/fujitsu/aoyg18lbca/aoyg18lbca_technical-manual_2344273062.webp)
- 56 -
DUC
T TYPE
ARYG18-5
4LHT
B
P
External heater output
Specifications of the signal output performance are as shown as follows:
Example:
When set temperature (Ts) is set at 22 °C;
• And room temperature (Tr) increase above 12 °C, signal output is on.
• And Tr increase above 21 °C, signal output is off.
• And Tr decrease below 19 °C, signal output is on.
• And Tr decrease below 10 °C, signal output is off.
The output also turns off in defrost operation.
Function
setting /
Rotary SW of External
input and output PCB
External output
Output
signal
Command
60-11 / D
Output of indoor unit
CN47
Low
→
High
Heater on
High
→
Low
Heater off
60-00 / 2
External input and output
PCB
Output 3
Off
→
On
Heater on
60-09 / B
60-10 / C
On
→
Off
Heater off
Output signal
Condition
Low
→
High
Heater turns on as shown in diagram of heating temperature
Off
→
On
High
→
Low
Heater turns off as shown in diagram of heating temperature
• Other than Heating mode
On
→
Off
• Error occurred
• Forced thermo off
• Fan stop protection
Off
Off
On
Tr-Ts
Tr-Ts=-1°C
Tr-Ts=-10°C
Tr-Ts=-3°C
Tr-Ts=-12°C
Содержание AOYG18LBCA
Страница 7: ...Part 1 INDOOR UNIT DUCT TYPE ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP ...
Страница 24: ... 18 DUCT TYPE ARYG18 54LHTBP 5 Wiring diagrams 5 1 Models ARYG18LHTBP and ARYG24LHTBP ...
Страница 25: ... 19 DUCT TYPE ARYG18 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 77: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18LBCA AOYG24LBCA AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA ...
Страница 96: ... 90 OUTDOOR UNIT AOYG18 54LB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Страница 97: ... 91 OUTDOOR UNIT AOYG18 54LB 4 2 Model AOYG30LBTA ...
Страница 98: ... 92 OUTDOOR UNIT AOYG18 54LB 4 3 Model AOYG36LBTA ...
Страница 99: ... 93 OUTDOOR UNIT AOYG18 54LB 4 4 Models AOYG45LBTA and AOYG54LBTA ...