![Fujitsu AOYG18LBCA Скачать руководство пользователя страница 22](http://html.mh-extra.com/html/fujitsu/aoyg18lbca/aoyg18lbca_technical-manual_2344273022.webp)
- 16 -
DUC
T TYPE
ARYG18-5
4LHT
B
P
4-4. Maintenance space requirement
For future maintenance and service access, provide sufficient maintenance space.
NOTE:
Do not place any wiring or illumination in the maintenance space, as they will impede
service.
Models: ARYG18LHTBP, ARYG24LHTBP, and ARYG30LHTBP
• Provide a service access for maintenance purposes.
• The service access necessary for fan units and filter maintenance.
Bottom view
AIR
Unit: mm
Control box
300 or more
500 or more
500 or more
Service access
AIR
Service access
Fan unit side
300 or more
500 or more
1400 or more
100
Bottom view
Unit: mm