6. Additional charge calculation
6-1. Models: AOYG18LBCA and AOYG24LBCA
Refrigerant charge
6-2. Models: AOYG30LBTA and AOYG36LBTA
Refrigerant charge
6-3. Models: AOYG45LBTA and AOYG54LBTA
Refrigerant charge
Refrigerant type
R410A
Factory charge amount
g
1,800
Total pipe length
m
15 or less
20
30 (Max.)
20 g/m
Additional charge amount
g
0
100
300
Refrigerant type
R410A
Factory charge amount
g
2,100
Total pipe length
m
20 or less
30
40
50 (Max.)
40 g/m
Additional charge amount
g
0
400
800
1200
Refrigerant type
R410A
Factory charge amount
g
3,350
Total pipe length
m
20 or less
30
40
50 (Max.)
40 g/m
Additional charge amount
g
0
400
800
1200
Содержание AOYG18LBCA
Страница 7: ...Part 1 INDOOR UNIT DUCT TYPE ARYG18LHTBP ARYG24LHTBP ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP ARYG54LHTBP ...
Страница 24: ... 18 DUCT TYPE ARYG18 54LHTBP 5 Wiring diagrams 5 1 Models ARYG18LHTBP and ARYG24LHTBP ...
Страница 25: ... 19 DUCT TYPE ARYG18 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 77: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG18LBCA AOYG24LBCA AOYG30LBTA AOYG36LBTA AOYG45LBTA AOYG54LBTA ...
Страница 96: ... 90 OUTDOOR UNIT AOYG18 54LB 4 Wiring diagrams 4 1 Models AOYG18LBCA and AOYG24LBCA ...
Страница 97: ... 91 OUTDOOR UNIT AOYG18 54LB 4 2 Model AOYG30LBTA ...
Страница 98: ... 92 OUTDOOR UNIT AOYG18 54LB 4 3 Model AOYG36LBTA ...
Страница 99: ... 93 OUTDOOR UNIT AOYG18 54LB 4 4 Models AOYG45LBTA and AOYG54LBTA ...