En-2

2.4. Electric requirement

•  Electric wire size and fuse capacity:

MODEL

12,000 ~ 14,000 BTU class

Power supply cord (mm

2

)

1.5

Connection cord (mm

2

)

1.5 or 1

Fuse capacity (A)

15

• Use conformed cable with Type245 IEC57.
• Install all electrical works in accordance to the national standard.
•  Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the 

units. (Both indoor unit and outdoor unit)

• Install the circuit breaker nearby the units.

2.5. Accessories

Drain pipe

1

2.6. Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.

Pipe length

15 m

20 m

Rate

Additional refrigerant

None

+100 g

20 g/m

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.

The maximum length of the piping is 20 m. If the units are further apart than this, correct 
operation can not be guaranteed.

Between 15 m and 20 m, when using a connection pipe other than that in the table, charge 
additional refrigerant with 20 g/1 m as the criteria.

3.  SELECTING THE MOUNTING POSITION

•  Decide the mounting position with the customer as follows:

•  Do not set to a place where there is oily smoke, oil is used in the factory, the unit can 

contact sea breeze, sul

¿

 de gases will be generated in the hot spring area, corrosive 

gases will be generated, animal may urine on the unit and ammonia will be generated 
and a dusty place.

3.1. Outdoor unit

(1)  If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

À

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3)  Do not install the unit where people pass.
(4)  Take you neighbors into consideration so that they are not disturbed by air blowing into their 

windows or by noise.

(5)  Provide the space shown in 

¿

 gure so that the air 

À

 ow is not blocked. Also for ef

¿

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(6)  Install the unit where keep away more than 3m from the antenna of TV set and Radio.
(7)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

 WARNING

Install at a place that can withstand the weight of the outdoor units and install positively 
so that the units will not topple or fall.

 CAUTION

Do not install where there is the danger of combustible gas leakage.

Do not install near heat sources.

In places where the outdoor temperature drops to 0 

Û

C or lower, the drain water may 

freeze and may stop up the drain or cause other outdoor unit trouble. Therefore take 
measures so that the drain water will not freeze and clog the drain.

In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with 
snow, it might become dif

¿

 cult to get warm and it is likely to cause of the breakdown. 

Please construct a canopy and a pedestal or place the unit on a high stand (local 
con

¿

 gured).

If children under 10 years old may approach the unit, take preventive measures so that 
they cannot reach the unit.

4. INSTALLATION DIAGRAM

Connection Cord

Conform to Type245 IEC57

[OUTDOOR UNIT]

10 cm or over

60 cm or over

10 cm or over

20 cm or over

25 cm or 
over

5 cm or over

INDOOR UNIT

Outdoor unit 
bottom

Drain pipe

Drain hose

•  Do not directly install it on the 

ground, otherwise it will cause 
failure.

•  To obtain better operation ef-

ficiency, when the outdoor unit 
is installed, be sure to open the 
front and left side.

54 cm

32 cm

 CAUTION

When the outdoor temperature is 0 

Û

C or less, do not use the accessory drain pipe 

and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 
freeze in extreme cold weather. (Reverse cycle model only)

In the area with heavy snowfall, if the intake and outlet of outdoor units blocked with 
snow, it might become dif

¿

 cult to get warm and it is likely to cause of the breakdown. 

Please construct a canopy and a pedestal or place the unit on a high stand (local 
con

¿

 gured).

5. INSTALLATION 

5.1. Outdoor unit installation

x

  Set the unit on a strong stand such as thing made of concrete blocks to minimize shock 

and vibration.

x

  Do not set the unit directly on the ground because it will cause trouble.

Switch cover A, B removal

(1) Remove the three tapping screws.
(2) Push downward the Switch cover B.
(3) Push upward the Switch cover A.

Installing the Switch cover A, B

(1)  After inserting the three hooks of Switch cover A, 

then push upward, and then tighten the two tap-
ping screws.

(2)  After inserting the three hooks of Switch cover B, 

then push upward, and then tighten the one tap-
ping screw.

 WARNING

Install the unit where it will not be tilted by more than 5°.

When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

Hook

Hooks

Hooks

Switch cover A

Switch cover B

9319205014_IM.indb   2

12/29/2010   11:53:14 AM

Содержание AOYG12LEC

Страница 1: ...Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CO...

Страница 2: ...After turning off the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as...

Страница 3: ...peration External connect kit UTY XWZX For control input output port Communication kit UTY XCBXZ1 For the installation of optional parts Optional communication kit is necessary for the installation 3 GENERAL This INSTALLATION MANUAL brieÀy outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all...

Страница 4: ... degrade the quality of the preserved or stored objects Do not install where there is the danger of combustible gas leakage Do not install the unit near a source of heat steam or Àammable gas Install the unit where drainage does not cause any trouble Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 m away from a television or radio rece...

Страница 5: ... taken to prevent drain water freezing Under low temperature environment when outdoor temperature under 0 C after cooling operation is executed water in the drain hose could be frozen Once drain water is frozen the drain hose will be blocked and water leakage may result at the indoor unit Installation method of Drain cap Use a hexagonal wrench 4 mm at opposite side to insert the drain cap till the...

Страница 6: ...with R410A Àare tools to achieve the speci ed Àaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 6 6 2 Bending pipes If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly ...

Страница 7: ...th a knife etc 1 Use crimp type terminals with insulating sleeves as shown in the gure below to con nect to the terminal block 2 Securely clamp the crimp type terminals to the wires using an appropriate tool so that the wires do not come loose Strip 10 mm Crimp type terminal Sleeve 3 Use the speci ed wires connect them securely and fasten them so that there is no stress placed on the terminals 4 U...

Страница 8: ...nd bottom piping overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap For left and left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap For left and left rear piping wrap the area which accommodates the rear p...

Страница 9: ...not be changed if invalid numbers or setting values are selected Refer to the installation manual enclosed with the remote control unit when the wired remote control unit option is used Entering the Function Setting Mode While pressing the POWERFUL button and SET TEMP simultaneously press the RESET button to enter the function setting mode STEP 1 Selecting the Remote Controller Signal Code Use the...

Страница 10: ...ate by the control unit or external input device Indoor room temperature sensor switching function Only for Wired remote controller The following settings are needed when using the Wired remote controller temperature sensor Ƈ Factory setting Setting Description Function Number Setting Value Ƈ No 42 00 Yes 01 If setting value is 00 Room temperature is controlled by the indoor unit temperature senso...

Страница 11: ... terminal L error Ɣ 6 Ɣ 10 Display PCB microcomputers communication error Ɣ 7 Ɣ 1 Discharge temp sensor error Ɣ 7 Ɣ 2 Compressor temp sensor error Ɣ 7 Ɣ 3 Outdoor unit Heat Ex liquid temp sensor error Ɣ 7 Ɣ 4 Outdoor temp sensor error Ɣ 7 Ɣ 5 Suction Gas temp sensor error Ɣ 7 Ɣ 6 2 way valve temp sensor error 3 way valve temp sensor error Ɣ 7 Ɣ 7 Heat sink temp sensor error Ɣ 8 Ɣ 2 Sub cool Heat E...

Страница 12: ... 7 9 3 Rimozione del pannello frontale 1 Rimuovere la griglia di aspirazione consultare le istruzioni per la rimozione della griglia di aspirazione 2 Rimuovere la copertura del cavo 3 Rimuovere le 3 viti ...

Страница 13: ... INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION...

Страница 14: ...the composition of the gas and liquid phases And always charge from the liquid phase where refrigerant composition is stable 2 2 Special tools for R410A Tool name Contents of change Gauge manifold Pressure is high and cannot be measured with a conven tional R22 gauge To prevent erroneous mixing of other refrigerants the diameter of each port has been changed It is recommended the gauge with seals ...

Страница 15: ...ight of the outdoor units and install positively so that the units will not topple or fall CAUTION Do not install where there is the danger of combustible gas leakage Do not install near heat sources In places where the outdoor temperature drops to 0 ÛC or lower the drain water may freeze and may stop up the drain or cause other outdoor unit trouble Therefore take measures so that the drain water ...

Страница 16: ... Bend the pipe with a radius of curvature of 70mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Tighten with two wrenches Torque wrench Wrench xed Flare nut Indoor unit pipe Connection pipe To prevent gas leakage coat the Àare surface with refrigerator oil Table 1 Flare nut size and tightening torque F...

Страница 17: ... TIMER indicator lamp of the indoor unit will simultaneously Àash slowly OUTDOOR UNIT 1 Is there any abnormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage 6 PUMP DOWN 6 1 Pump down PUMP DOWN OPERATION FORCED COOLING OPERATION To avoid discharging refrigerant into the atmosphere at the time of relocation or disp...

Отзывы: