- 75 -
DUC
T TYPE
ARYG12-5
4LHT
B
P
11) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially activated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy
saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
12) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number
Setting value
Setting description
Factory setting
49
00
Disable
01
Enable
02
Remote controller
♦
Function number
Setting value
Setting description
Factory setting
60
00
Operation status
♦
01 - 08
(Setting prohibited)
09
Error status
10
Indoor unit fan operation status
11
External heater
Содержание AOYG12LBLA
Страница 26: ... 20 DUCT TYPE ARYG12 54LHTBP 5 Wiring diagrams 5 1 Models ARYG12LHTBP ARYG14LHTBP ARYG18LHTBP and ARYG24LHTBP ...
Страница 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Страница 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Страница 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...
Страница 113: ... 107 OUTDOOR UNIT AOYG12 54LB 5 5 Models AOYG45LBTA and AOYG54LBTA ...