- 123 -
O
U
T
D
OOR UNIT
AOY
G
12-
54LB
10. Electrical characteristics
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate
devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
Model name
AOYG12LBLA
AOYG14LBLA
AOYG18LBCA
AOYG24LBCA
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
10.5
13.0
13.5
18.5
Wiring
spec. *2
Circuit breaker
current
A
25
25
25
30
Power cable
mm
2
4.0
Connection
cable *3
mm
2
1.5 — 2.5
Limited
wiring
length
m
26
31
Model name
AOYG30LBTA
AOYG36LBTA
AOYG45LBTA
AOYG54LBTA
Power
supply
Voltage
V
230 ~
Frequency
Hz
50
Max operating current *1
A
17.0
20.0
22.5
23.5
Wiring
spec. *2
Circuit
breaker
current
A
30
Power cable
mm
2
4.0
6.0
Connection
cable *3
mm
2
1.5 — 2.5
Limited
wiring
length
m
51
Содержание AOYG12LBLA
Страница 26: ... 20 DUCT TYPE ARYG12 54LHTBP 5 Wiring diagrams 5 1 Models ARYG12LHTBP ARYG14LHTBP ARYG18LHTBP and ARYG24LHTBP ...
Страница 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Страница 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Страница 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...
Страница 113: ... 107 OUTDOOR UNIT AOYG12 54LB 5 5 Models AOYG45LBTA and AOYG54LBTA ...