Characteristics of air volume and capacity
• Cooling
• Heating
Automatic airflow adjustment procedures
1. To start the auto setting, use No.32 of setting value in Function Number 26.
2. Run the air conditioner on fan mode (High).
* For instructions on how to operate the air conditioner, refer to the operation manual of the re-
mote controller.
During automatic airflow adjustment, the mode will be fixed at fan (High).
When this function is active, do not operate the outdoor unit.
3. The air conditioner will run for about 1 to 8 min then stop automatically.
* Do not change the throttles of the inlet and outlet ports during operation.
When used in a group control system, the setting will take about 10 min.
4. Turn the air conditioner off and on again.
5. Check the setting value of Function 26.
* If the setting value has not changed, repeat the procedure from step 2.
!
CAUTION
When the duct or outlet installations are changed after the Automatic airflow adjustment is com-
pleted, repeat the procedure from step 1.
[l/s]
[m
3
/h]
Airflow
139
278
417
556
972
500
1000
1500
2000
3500
833
3000
695
2500
100
105
95
Capacity [
%
]
[l/s]
[m
3
/h]
Airflow
139
278
417
556
972
500
1000
1500
2000
3500
833
3000
695
2500
100
105
95
Capacity [
%
]
Содержание AOYG12LBLA
Страница 26: ... 20 DUCT TYPE ARYG12 54LHTBP 5 Wiring diagrams 5 1 Models ARYG12LHTBP ARYG14LHTBP ARYG18LHTBP and ARYG24LHTBP ...
Страница 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Страница 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Страница 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...
Страница 113: ... 107 OUTDOOR UNIT AOYG12 54LB 5 5 Models AOYG45LBTA and AOYG54LBTA ...