6. Capacity compensation rate for pipe length and height
difference
6-1. Models: AOYG12LBLA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
25
Height differenc
e
H (m)
Indoor unit is higher than
outdoor unit *1
15
-
-
-
0.903
0.894
0.867
10
-
-
0.964
0.918
0.909
0.881
7.5
-
0.988
0.968
0.922
0.912
0.885
5
0.992
0.992
0.972
0.925
0.916
0.888
0
1.000
1.000
0.980
0.933
0.923
0.895
Indoor unit is lower than
outdoor unit *2
-5
1.000
1.000
0.980
0.933
0.923
0.895
-7.5
-
1.000
0.980
0.933
0.923
0.895
-10
-
-
0.980
0.933
0.923
0.895
-15
-
-
-
0.933
0.923
0.895
HEATING
Pipe length (m)
5
7.5
10
15
20
25
He
igh
t differ
ence
H (m)
Indoor unit is higher than
outdoor unit *1
15
-
-
-
0.943
0.916
0.896
10
-
-
1.010
0.943
0.916
0.896
7.5
-
1.000
1.010
0.943
0.916
0.896
5
1.000
1.000
1.010
0.943
0.916
0.896
0
1.000
1.000
1.010
0.943
0.916
0.896
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.995
1.005
0.939
0.912
0.892
-7.5
-
0.993
1.002
0.936
0.909
0.890
-10
-
-
0.999
0.934
0.907
0.887
-15
-
-
-
0.925
0.898
0.878
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
Содержание AOYG12LBLA
Страница 26: ... 20 DUCT TYPE ARYG12 54LHTBP 5 Wiring diagrams 5 1 Models ARYG12LHTBP ARYG14LHTBP ARYG18LHTBP and ARYG24LHTBP ...
Страница 27: ... 21 DUCT TYPE ARYG12 54LHTBP 5 2 Models ARYG30LHTBP ARYG36LHTBP ARYG45LHTBP and ARYG54LHTBP ...
Страница 110: ... 104 OUTDOOR UNIT AOYG12 54LB 5 Wiring diagrams 5 1 Models AOYG12LBLA and AOYG14LBLA ...
Страница 111: ... 105 OUTDOOR UNIT AOYG12 54LB 5 2 Models AOYG18LBCA and AOYG24LBCA 5 3 Model AOYG30LBTA ...
Страница 112: ... 106 OUTDOOR UNIT AOYG12 54LB 5 4 Model AOYG36LBTA ...
Страница 113: ... 107 OUTDOOR UNIT AOYG12 54LB 5 5 Models AOYG45LBTA and AOYG54LBTA ...